⚡NEN-Hub
🔍
IEC 60364-6 / NEN-EN-IEC 61557-4

Measuring protective conductor continuity (PE)

Available in: en, nl, pl, ru, ua
Norm edition: NEN 3140:2011+A3:2019
Section: VPNorm reference: NEN 3140:2011+A3:2019

AI-checked: automatically reviewed for norm references, not yet assessed by a qualified person. This page has not yet been technically reviewed by a qualified person. Always check the current standard and your own appointment (aanwijzing); this is not a substitute for NEN 3140 or NEN 1010.

Updated: ≈ 4 min read

Measuring protective conductor continuity (PE)

The measuring-instruments-and-CAT guide names the low-resistance instrument as the right tool for the continuity of the protective conductor and equipotential bonding, and gives the formula R = ρ·L/A for an expected value. The measurement-sequence guide places this test among the first, de-energised measurements. This article covers the technique itself: how to check and judge the continuity of the protective conductor across a full circuit.

The instrument: ≥ 200 mA, not an ordinary multimeter

This test calls for an instrument conforming to NEN-EN-IEC 61557-4 (resistance of earth connections and equipotential bonding) with a test current of at least 200 mA. An ordinary multimeter or continuity buzzer uses a very small current: it only confirms that a connection exists, does not break through an oxide film on a terminal, and says nothing about the quality of the connection. For background on the instruments see the IEC 61557 guide.

Before every series of measurements: short the test leads together and zero (compensate) the instrument so the lead resistance does not end up in the result. If the lead is too short, use an extension lead on a reel and zero including that lead.

Method 1 — direct measurement

  1. Isolate and prove dead (lock out, see the measurement-sequence guide).
  2. Connect one test lead to a reliable reference point: the earth bar / PE terminal in the distribution board.
  3. Touch the other test lead to the point to be checked: the PE terminal of the socket outlet, the earth terminal of the appliance, or the accessible conductive part under test.
  4. Read the resistance and record the value for each measuring point.

Method 2 — loop method (outward and return path in one measurement)

This method (called the "R1+R2 method" in English-language literature) is convenient for assessing a complete circuit in one go:

  1. Isolate and prove dead.
  2. At the origin of the circuit (distribution board) temporarily connect the line conductor and the protective conductor of that circuit with an auxiliary link.
  3. At the furthest connection point, measure with the low-resistance instrument between the line and PE terminals. The result is the sum of the resistance of the line conductor and the protective conductor.
  4. Remove the link and restore the original connection before the circuit is re-energised.

The result is a building block for an estimate of the fault-loop impedance (network impedance upstream of the installation + resistance of the line and protective conductors). Adding the values arithmetically is an approximation; assess the fault-loop impedance itself with a loop-impedance measurement (see the loop-impedance Zs guide).

Judging: compare with an expected value

Compare the measured value with a pre-calculated expected value (R = ρ·L/A per conductor, see the measuring-instruments-CAT guide) rather than just noting "continuity yes/no". A broken protective conductor gives infinite resistance and is obvious, but a subtly raised value — from an oxidised terminal or a loosened connection — still gives a reading, just too high.

There is no universal maximum value for all situations: what is acceptable depends on cross-section, length and the protective device of the circuit. Use the calculated expected value and the design data of the installation, and check whether the standard or inspection protocol you work to states a limit value.

Note: for a circuit with several branches, measure to the furthest point of each branch — the highest measured value governs, not the average.

Parallel paths distort the measurement

Metal pipes, cable trays and the equipotential bonding can form a parallel path so that the reading is lower than that of the protective conductor under test. How to recognise and avoid this is covered in Checking PEN continuity in practice.

Common mistakes

  1. Forgetting to remove the link before re-energising — this creates a permanent, direct connection between line and protective conductor.
  2. Using an ordinary multimeter instead of an instrument with ≥ 200 mA — a poor connection stays masked.
  3. Not zeroing the test leads, so lead resistance is included.
  4. Judging only "continuity yes/no" instead of comparing the value with the expected value.
  5. Not measuring to the furthest point or skipping a branch.

Further reading

Related terms
Measuring protective conductor continuity (PE) · NEN-Hub