Errors we found and fixed are listed here. Spotted something wrong? Report it via the link at the bottom of any guide.

Report an error

  • 2026-11-07

    Glossary: term "SELV" (RU/UA/EN/PL description)

    The RU and UA translations said "damp-fibrous zones" (a mistranslation of "wet and damp zones"); corrected. The description also began with the term itself as a prefix; removed.

  • 2026-11-07

    Guide: horticulture and greenhouses (§705); glossary: "NIPT"; references to IEC 60446; a typo in an answer option

    Greenhouses: the requirement "minimum IP55 / IP67" and "300 mA RCD on circuits > 32 A" could not be traced to the standard; replaced by minimum IP44 (IEC 60364-7-705), 30 mA RCD on socket-outlets up to 32 A and an RCD of at most 300 mA as fire protection; clause numbers are still to be verified. "NIPT" turned out to be an invented acronym and was removed from the glossary (the term is now "Working dead / Spanningsloos werken"; the RU/UA/PL translations even said the opposite, "working under voltage"). IEC 60446 was merged into NEN-EN-IEC 60445 and is named that way. Two questions that attributed a fixed inspection interval or a sticker requirement to NEN 3140 are now drafts.

  • 2026-11-07

    Guide: danger zone and approach zone, theory practice question 14, danger-zones diagram

    The fixed distances "≈ 0 mm" (danger zone) and "≈ 300 mm" (approach zone) were removed: they were not tied to a verifiable source, and the distances depend on the voltage and are given in the standard's tables. The page now points to those tables. Exact values will follow after review by a qualified reviewer.

  • 2026-10-03

    Guides: current-time curve (IEC 60479-1), arc flash, theory practice questions, overvoltage categories, exceptions §433.3/§434.3

    Physiological thresholds aligned: perception about 0.5 mA, let-go about 10 mA, ventricular fibrillation from about 40 mA for exposure of seconds (curve c1). Some pages previously said 0.25–1 mA, 5 mA and 50 mA, and "atrial fibrillation"; the statement that 30 mA is "well below the let-go threshold" was also wrong (30 mA is above it). Added: impulse withstand voltages per overvoltage category (230/400 V: 1.5/2.5/4/6 kV) and the remaining exceptions of §433.3.1.

  • 2026-10-03

    Guides: MCCB vs. MCB, §433, fire extinguishers, sauna (§703), §524, distribution-board diagram, first aid

    MCCB: the conventional tripping current is 1.30 × In (IEC 60947-2), not 1.45 × In as for an MCB (IEC 60898-1); the sentence saying IEC 60898-1 "does not apply" for ordinary persons was replaced by the actual difference in user group and current range. EN 3-11 only covers small Li-ion batteries (up to about 600 Wh). Sauna: zone 3 requires equipment rated for at least 125°C. Distribution-board diagram: assumed reasons are now marked as such. A table number and a Red Cross attribution were removed because we could not verify them.

  • 2026-10-02

    Practice question on the BA4/BA5 classification (practical bank)

    The labels were swapped: BA5 = skilled (VP), BA4 = instructed (VOP). The question now refers to the VP/VOP roles of NEN 3140 / NEN-EN 50110-1; the BA classes come from IEC 60364-5-51 (NEN 1010 §512). The glossary entry was updated.

  • 2026-10-02

    Guide: measuring protective conductor continuity

    Fully rewritten using Dutch terminology (instrument ≥ 200 mA per NEN-EN-IEC 61557-4, direct and loop method, zeroing). The British term "R1+R2" was replaced throughout the guides.

  • 2026-10-02

    Guides and questions that cite the Bouwbesluit

    The Bouwbesluit 2012 was replaced by the Besluit bouwwerken leefomgeving (Bbl) on 1 January 2024. References were updated and an unverifiable article number was removed.

  • 2026-10-02

    Test results and certificate page

    Made clearer that a result is a practice result, not an NEN 3140 certificate; a VP/VOP/LP designation only follows from a written designation by the employer.

  • 2026-10-02

    Ukrainian translations (12 guides and the glossary)

    Russian terms (УЗО, утечки) replaced with the Ukrainian ones (ПЗВ, витоку).

  • 2026-10-03

    Measuring-instrument CAT; EV charging (§722); arc flash and PPE

    Meter cupboard/main fuse is CAT IV (not CAT III); wallbox DC detection now cites only IEC 62955; NFPA 70E thresholds are marked as a US orientation (Europe: IEC 61482-1-1/-1-2) and the ≤ 40 cal/cm² row was added; the 40-question guide was renamed to practice questions (not official exam questions).

  • 2026-11-06

    Numbers on the site (home, About, Badges, 404) and badge names

    Previously shown counts of learners, passes and badge holders included test accounts and single practice questions and were therefore far too high. All figures now come from one module that counts only registered, real users; numbers below 50 are not shown. Badges are no longer called “certified” but “mock exam passed”, because a practice result is not a certificate.