Fire extinguishers for electrical installations — there is no separate "fire class E", but there is a separate voltage test
The arc flash guide briefly mentions that only a CO₂ or powder extinguisher should be used for a fire caused by an electrical fault. This article goes deeper into why that is the case, and into the distinction between an extinguisher's fire-class rating and the separate suitability assessment for use on installations that may still be live.
There is no official "fire class E" for electricity
EN 2 (Classification of fires) defines classes A (solids), B (liquids), C (gases), D (metals) and F (cooking fats/oils). There is no class E for electrical fires: the European reasoning is that electricity is an ignition source, not a combustible substance in itself — the burning material (for example a cable's plastic insulation) already falls under class A. Some older extinguishers, and some non-European classifications, carry an electrical symbol (a lightning bolt), but this is not an official EN 2 fire class and must not be read as one.
Note: the lightning-bolt symbol on an extinguisher therefore says nothing about "which fire" it extinguishes — that remains class A/B/C/D/F — but it does indicate whether the extinguisher may safely be used while the installation may still be live.
The separate dielectric suitability test
In addition to the regular fire-class type approval, extinguishers that must be suitable for use on installations that may be live undergo a separate dielectric test, which demonstrates that the operator cannot receive a dangerous current back through the extinguishing jet at a given test voltage and distance. This has direct consequences for extinguisher selection:
- CO₂ extinguishers and powder extinguishers are inherently non-conductive and are generally considered safe for use on electrical installations, provided they are used at the correct distance.
- Water extinguishers and foam extinguishers are conductive in their basic form and are therefore not automatically suitable for use on an installation that may still be live — only a version explicitly dielectric-tested and certified for this purpose (identifiable by the marking on the extinguisher's nameplate, not by a pictogram) may be used.
What EN 3-7 actually specifies
The dielectric suitability of a portable extinguisher is tested under EN 3-7. Extinguishers that pass may be marked as suitable for use on live installations up to 1000 V at a distance of at least 1 metre (the usual "1000 V / 1 m" marking). Note the limits:
- the value applies to low voltage; on medium or high voltage you do not fight the fire with a portable extinguisher — you isolate, or wait for the fire brigade;
- it is a manufacturer's marking after testing, not a general property of the agent — check the nameplate and documentation;
- the 1 m distance must actually be kept while extinguishing; with a DC source (PV, battery) you cannot switch off, the installation stays live even after "switching off".
(Do not confuse with IEC 61243: that is the standard for voltage detectors, not for extinguishers.)
Lithium-ion fires are a special case
A fire in a lithium-ion battery (energy storage, UPS, e-bike, EV) is not an ordinary fire: through thermal runaway the cell can keep heating itself, reignite hours later and release toxic gases (including hydrogen fluoride). An ordinary powder or CO₂ extinguisher knocks down the flame but does not cool the cell. EN 3-11 exists for this: additional requirements and tests on top of EN 3-7 for extinguishers suited to fires in small Li-ion batteries (up to about 600 Wh, e.g. e-bike or laptop batteries). For a larger battery (container, rack, UPS room): leave the room, close the door, call 112, do not fight it with a portable extinguisher, and tell the fire brigade the battery type. See also the guides on lithium BMS and UPS.
Practical relevance
When assembling a firefighting-equipment plan for a space with electrical installations (switchgear room, server room, machine hall), it must be explicitly established whether the extinguishers present are approved for use on live parts — this is separate from the regular fire-class suitability (A/B/C/D/F) shown on the extinguisher label. An extinguisher that is perfectly suitable for a class A fire is not automatically also safe to use on a burning distribution board that may still be live.
Common mistakes
- Assuming a "suitable for electrical equipment" sticker is an official EN 2 fire class — this is a separate voltage-suitability assessment, not a fire class E.
- Placing a water or foam extinguisher near a switchboard without verifying that it is specifically dielectric-tested and certified for use on live installations.
- Opening a burning distribution board directly to extinguish it — as also described in the arc flash guide, an arc can reignite when opened due to the sudden inrush of oxygen, regardless of which extinguishing agent is used.
Related
Further reading
- NEN-EN 50110-1First aid for electrical accidents — rescue and resuscitation
- §5RI&E for Electrical Equipment
- IEC 61140Protection class I, II and III — IEC 61140
- §3.6Danger zone and approach zone — the three types of electrical work
- InspectiePeriodic inspection of EV charge points under NEN 3140
- §6.3Working De-energized — The 5 Steps (LOTO)