NEN 1010 §414
SELV
SELV (Safety Extra Low Voltage)
Also known as: selv, badkamer, badkamers, waterzone
SELV (Safety Extra Low Voltage): Safe extra-low voltage ≤50 V AC / 120 V DC, supplied via a safety transformer with double insulation. No earthing of active parts or enclosures permitted. Used in wet and damp zones such as zone 0 in bathrooms.
Practical example
Lighting in zone 0 of a bathroom is powered via a 12 V SELV transformer with no earth connection on the secondary circuit.
Common mistake
SELV (Safety Extra Low Voltage) Common mistake: Connecting a SELV circuit to PE 'just in case' — contradicts SELV definition and breaks double insulation.
See also
Related terms
In-depth guides
- → Earthing and earthing systems (TN, TT, IT)
- → §414 SELV, PELV & FELV — the extra-low-voltage measure
- → §715 / IEC 60364-7-715 §715 — Extra-low-voltage lighting installations
- → §131 Protection Principles
- → §411.3.2 Automatic disconnection of supply (AUV)
- → §413.3 Electrical separation (§413.3) — an isolating transformer as a protective measure without earthing