⚡NEN-Hub
🔍
NEN 1010 §411.3.2

Automatic disconnection of supply (ADS)

Automatische uitschakeling van de voeding
Also known as: afo, afschakeling, automatic-disconnection, beschermende-uitschakeling, protective-disconnection, 411

Automatic disconnection of supply – main protective measure: upon fault to PE, overcurrent protection or RCD must disconnect within required time (≤0.4 s for 230 V final circuits).

Practical example

Automatic disconnection of supply. For a fault on a 230 V final circuit, loop impedance must be low enough for the breaker to trip within 0.4 s; a long cable requires an RCD.

Common mistake

Automatic disconnection of supply Common mistake: Relying solely on the MCB's rated current without measuring loop impedance — excessive Zs results in a tripping time well exceeding the required limit.