SELV, PELV & FELV — the extra-low-voltage measure

Available in: en, nl, pl, ru, ua
Updated: ≈ 3 min read

§414 — SELV, PELV & FELV — the extra-low-voltage measure

SELV, PELV and FELV are three variants of extra-low voltage, but only two of them count as a full protective measure against electric shock. §414 treats this as a general principle, independent of a specific space — the bathroom guide (§701) applies this principle only within the context of wet locations; §414 itself applies everywhere extra-low-voltage circuits are used (garden lighting, playground equipment, control circuits of machines, and so on).

The limit values

Dry/normal conditionsDamp/wet conditions
SELV / PELV50 V AC / ≤ 120 V DC25 V AC / ≤ 60 V DC

Below these values, no additional protection against direct contact is generally required; below 25 V AC in dry conditions, the need for basic protection even disappears in many practical situations (depending on surface contact and environment).

SELV versus PELV versus FELV

Separation from the mainsEarthingFull protective measure?
SELV (Safety Extra-Low Voltage)Full galvanic separation via safety transformerNot earthedYes
PELV (Protective ELV)Full galvanic separationMay be earthed at one pointYes
FELV (Functional ELV)No full safety separation — functional reason for low voltage (e.g. operating comfort), not safety separationVariableNo

The crucial difference: SELV/PELV require a safety transformer (or equivalent separation) that fully separates the extra-low-voltage circuit from higher voltages. A FELV circuit can have an extra-low voltage without this separation — for example, a transformer that steps down voltage purely for functional purposes, not for safety separation. Such a circuit may not be regarded as the sole protective measure: additional basic protection is required, as if it were an ordinary low-voltage circuit.

Practical applications

  • Garden and outdoor lighting: often implemented as SELV (12V/24V) to limit the risk of contact during digging work or with damaged cables. NEN 1010:2020 §715.414.1 even prescribes exclusively SELV for extra-low-voltage lighting — PELV is not sufficient here.
  • Machine control circuits: often FELV — functionally low voltage (e.g. 24V DC PLC control), but without safety separation, so the panel still requires full basic protection.
  • Play equipment and swimming pool lighting: SELV with the stricter 25V/60V limit due to the damp/wet environment.

Common mistakes

  1. Regarding every low voltage as "safe" — a FELV circuit can have the same voltage as SELV but lacks the safety separation; it does not protect in the same way.
  2. Applying PELV where §715.414.1 requires SELV — for extra-low-voltage lighting, PELV (with its earthing point) is not permitted as a substitute for SELV.
  3. Applying the dry-conditions limit (50V/120V) in wet locations — the stricter 25V/60V limit applies as soon as the environment is damp/wet (compare the bathroom zones in §701).
  4. Assuming that a galvanically separated transformer automatically produces SELV — if the secondary circuit is earthed at even a single point, it is by definition PELV, not SELV; this distinction is relevant for which applications are permitted (see §715.414.1 above).

Further reading

Related terms
SELV, PELV & FELV — the extra-low-voltage measure · NEN-Hub