RCD test (trip time)
RCD-test (uitschakeltijd)
Also known as: rcd-test, aardlek-test, testknop, maandelijkse-test
Verifies RCD tripping at 1×In ≤300 ms and 5×In ≤40 ms. Also perform a zero-current test (½×In — must not trip) and, if specified, a fault test.