Prospective short-circuit current

Prospectieve kortsluitstroom (Ik)
Also known as: kortsluitstroom, ik, short-circuit, short-circuit-current, prospective-short-circuit, kortsluitstroom-berekening, icc-transformator, uk-4-procent-icc

Prospective short-circuit current (Ik). The current that would flow at a dead short at the measured point. Determines whether the switching equipment has the breaking capacity to safely interrupt that current — typically 6 kA for final circuits, 10–25 kA in distribution boards.

Practical example

Prospective short-circuit current (Ik). At a distribution board near the transformer, an Ik of 15 kA is measured; the installed switching equipment must have a breaking capacity of at least that value.

Common mistake

Prospective short-circuit current (Ik). Common mistake: Selecting switching gear based on rated current only, without checking prospective short-circuit current — the breaker may self-damage during a real short circuit.