⚡NEN-Hub
🔍

RCD Type B

Also known as: type-b-rcd, rcd-type-b-vfd, frequentieregelaar-rcd, vfd-aardlekschakelaar, ev-rcd-type-b, dc-lekstroom, vfd-type-b-rcd, capacitieve-lekstroom-vfd, vfd-pe-10mm

Detects smooth DC leakage currents up to 1 kHz+. Required for three-phase inverters (PV panels, EV chargers without galvanic isolation) where Type A does not ensure safety—a DC leakage blocks magnetic operation.

Practical example

RCD Type B Example: A three-phase EV charger without galvanic isolation in the inverter is protected by a Type B RCD, as smooth DC faults would otherwise go undetected.

Common mistake

Common mistake: Using a Type A RCD with a non-isolated inverter — smooth DC leakage current can saturate the RCD's magnetic core, preventing tripping.

See also

Beschikbaar in: English, Nederlands, Polski, Русский, Українська
RCD Type B — dictionary · NEN-Hub