Cable resistance (R) and reactance (X) in voltage-drop calculations — when X may and may not be neglected
Cable resistance (R) and reactance (X) in voltage-drop calculations — when X may and may not be neglected
The guide on §525 — Voltage drop covers the recommended 3% and 5% voltage-drop limits and a practical rule-of-thumb formula based on resistance alone. This guide goes deeper into the question of when that simplified formula suffices and when the cable's inductive reactance must also be taken into account.
The full formula from Annex G
Annex G of IEC 60364-5-52 gives the voltage drop as a function of
both the resistance R and the reactance X of the cable per unit
length:
ΔU = b × Ib × L × (R cos φ + X sin φ)
where b = 2 for a single-phase circuit and b = √3 for a three-phase
circuit, Ib is the load current, L is the cable length, R and X
are the resistance and reactance per unit length of the cable
respectively, and φ is the phase angle between voltage and current of
the load.
Why R dominates for small cross-sections
The ohmic resistance R of a conductor is inversely proportional to
its cross-section (R = ρ / A): the larger the cross-section, the
smaller the resistance per unit length. The inductive reactance X of
a cable at 50 Hz, by contrast, depends mainly on the geometric layout
of the cable (spacing between conductors, number of cores) and changes
relatively little with cross-section — a commonly used practical value
for the reactance of low-voltage cables is on the order of 0.08
Ω/km per phase, regardless of whether the cross-section is small or
medium-sized.
The result is that at small cross-sections R is much larger than X,
so the contribution of the X sin φ term to the total voltage drop is
negligibly small. As the cross-section increases, R decreases while
X stays roughly constant, shifting the ratio between the two and
giving the reactance an increasingly larger share of the total voltage
drop.
The threshold: 50 mm² copper / 70 mm² aluminium
According to Annex G of IEC 60364-5-52, the reactance may be neglected for cables with a cross-section of up to and including 50 mm² for copper and up to and including 70 mm² for aluminium — in that range, the simplified formula with only the resistive term suffices:
ΔU (%) = (b × Ib × cos φ × L × 100) / (γ × A × U₀)
where γ is the conductivity of the material at operating temperature
and A is the cross-section in mm². Above those cross-section
thresholds, the full formula with both R and X must be used,
because omitting the reactance term then leads to a noticeably too-low
calculated voltage drop.
Why this matters in practice
For a large-consumer connection, a long feeder cable to a sub- distribution board, or a cable to a charging plaza with multiple EV chargers, a cross-section of 70, 95, 120 mm² or larger is often used. At those cross-sections, the cable is above the 50 mm² threshold (for copper), and the simplified R-only formula yields a voltage drop that comes out lower than the actual value — with the risk that an installation appears on paper to stay within the 5% limit, while the actual voltage drop exceeds it.
Practical relevance
When sizing cables with a cross-section around or above the 50/70 mm²
threshold, it is important not to blindly carry over the simplified
rule-of-thumb formula from an earlier, smaller sizing exercise, but to
use the full R and X values from the cable specification or from Annex
G of IEC 60364-5-52. For circuits with a low power factor (cos φ), such
as certain motor-starting circuits, the X sin φ term also carries
extra weight, even when the cross-section is just below the threshold.
Common mistakes
- Applying the simplified R-only formula to a cable above 50 mm² copper (or 70 mm² aluminium) — this underestimates the actual voltage drop because the reactance contribution is left out.
- Assuming reactance scales proportionally with cross-section the way resistance does — X changes only slightly with cross-section in approximation, while R decreases inversely with it, so the ratio between the two actually shifts at larger cross-sections.
- Ignoring the reactance term for a low-cos φ load (for example a
starting motor) — the
X sin φcontribution is larger the largersin φis, so reactance carries more weight precisely at a low cos φ than at a load with cos φ close to 1. - Using generic R and X table values without accounting for the cable construction (single-core vs. multi-core, conductor spacing) — the exact reactance value depends on the geometry of the cable; for an accurate calculation, the cable manufacturer's data or the tables in Annex G apply.
Related
Further reading
- NEMA MG1 Part 30/31Motor cable length with variable frequency drives — voltage reflection and choosing between a dv/dt and a sine-wave filter
- §543.1 (IEC 60364-5-54)Steel wire armour as a protective conductor — why the armour's cross-section must be verified in its own right
- IEC 60287-1-1Skin effect and proximity effect at large cable cross-sections — why AC resistance exceeds DC resistance
- NEN 1010 §526Connecting aluminium and copper — bimetallic corrosion and why cross-section doesn't scale 1-to-1
- IEC 61439-6Busbar trunking systems (IEC 61439-6) — when to use them instead of cable
- DLRO / IEC 62271Contact resistance testing with a micro-ohmmeter (DLRO) — verifying joints that thermography can miss