§705

Greenhouses and Horticultural Enterprises

Available in: en, nl, pl, ru, ua
Norm edition: NEN 1010:2020+C1:2024
Section: GreenhousesNorm reference: NEN 1010:2020+C1:2024, 705

AI-checked: automatically reviewed for norm references, not yet assessed by a qualified person. This page has not yet been technically reviewed by a qualified person. Always check the current standard and your own appointment (aanwijzing); this is not a substitute for NEN 3140 or NEN 1010.

Updated: ≈ 1 min read

§705 — Horticultural Enterprises and Greenhouses

Special room with elevated risks: moisture, mechanical damage, fire hazard during CO₂ fertilization and assimilation lighting.

Requirements

  • Minimum IP44 for equipment in the greenhouse (IEC 60364-7-705, art. 705.512.2); a higher IP rating may be needed because of the environment (spraying, cleaning, dust) and follows from the risk assessment per room.
  • 30 mA RCD on socket-outlets up to 32 A and on final circuits for portable equipment.
  • RCD of at most 300 mA as fire protection for the other circuits (see NEN 1010 §705).
  • Verification of the exact clause numbers and IP requirements by a reviewer is pending (needs-human).
  • Main equipotential bonding on metal gutters, walkways, and CO₂ pipes.

Practice in Westland greenhouses

  • Assimilation luminaires (HPS 600/1000 W or LED): keep in mind that HF interference can blind RCD type A — type F or B is recommended.
  • Pt1000 sensors for climate control: see Practical → Pt1000 3-wire connection.
  • Many inverters on one RCD → cumulative leakage current check mandatory.
  • Priva, Hoogendoorn, Hortimax — note proprietary connectors, but the 1010 requirements apply in full.

Further reading