Distribution boards & selectivity between protective devices
§536 — Distribution boards & selectivity between protective devices
Selectivity (also called discrimination) means that, in the event of a fault, only the protective device closest to the fault trips — the rest of the installation stays in operation. Without selectivity, a short circuit in a single circuit can sometimes take down the whole main group or even the entire building.
Note on status: the selectivity provisions in §536 are, in the Netherlands, informative, not mandatory. NEN 1010 does require (via the division into circuits) that an installation be built up so that a fault in one circuit does not unnecessarily drag down other circuits — selectivity is the practical implementation of that requirement, not a stand-alone statutory obligation.
Why split an installation into circuits?
- Limits the consequences of a single fault to one part of the installation.
- Allows maintenance on one circuit without shutting down the rest.
- Simplifies fault-finding: a tripped circuit points directly to the problem area.
The 1.6:1 rule of thumb for fuses
For fuses according to NEN-EN-IEC 60269-1 of the same type (e.g. gG), with a rated current ≥ 16 A, the following applies: full selectivity between two fuses connected in series is guaranteed if the ratio between the rated currents is ≥ 1.6 : 1 (for example, a 25 A fuse upstream of a 16 A fuse).
For miniature circuit breakers (MCBs) this rule of thumb cannot simply be applied — circuit breakers of the same type/brand must be checked against the manufacturer's selectivity tables, especially for short-circuit currents. A larger current difference between two circuit breakers increases the likelihood of selectivity, but does not automatically guarantee it the way it does for fuses.
Types of selectivity
| Type | How it works |
|---|---|
| Current selectivity | The upstream protective device has a higher trip current — works mainly for lower fault currents. |
| Time selectivity | The upstream protective device trips with a delay (see also selective type S RCD, §531). |
| Energy selectivity (I²t) | Based on the let-through energy of fuse links — the downstream fuse melts before the upstream device lets through energy that would cause damage. |
| Full vs. partial selectivity | Full = selective up to the maximum short-circuit current; partial = selective up to a certain current value, above which both devices trip. |
Distribution board layout
Practical layout rules that are common in new-build dwellings:
- At least 2 residual current devices of 30 mA, so that a leakage current does not de-energize the entire dwelling.
- Maximum 4 final circuits per RCD — a rule of thumb to limit cumulative leakage current (§531: must stay below 30% of I∆n) and the "domino effect" in the event of a fault.
- A main switch upstream of all circuits, directly accessible.
- Circuit layout such that comparable loads (lighting separate from socket outlets, kitchen separate from the rest) don't let a fault unnecessarily radiate into unrelated rooms.
Common mistakes
- Combining circuit breakers from different brands and assuming they are selective — selectivity tables are brand- and type-specific, and are never simply interchangeable.
- Too few circuits — a dwelling with only 1 RCD for the entire installation has no selectivity whatsoever: any leakage current shuts everything down.
- Confusing overload selectivity with short-circuit selectivity — two circuit breakers can be selective at low overload currents but not at a short circuit close to the source.
- Applying the 1.6:1 rule to circuit breakers instead of only to fuses of the same type — this leads to false confidence.
Related
- §531 — Residual Current Devices (RCD): selective type-S RCD as a form of time selectivity.
- MCB B/C/D characteristics: tripping characteristics that affect selectivity calculations.
- Fuse links: I²t values for energy selectivity.
Further reading
- §559Assimilation lighting — group division, RCD type and protection for greenhouse lighting
- NEN-EN-IEC 62305Lightning protection for greenhouse complexes — risk analysis and protection level
- §434Short-circuit protection & the adiabatic equation — §434
- §443Surge Protection (SPD)
- §560Emergency & Escape Route Lighting — §560
- §559Lighting Installations — §559