Reference methods — determining the installation method for the current-carrying-capacity table
Reference methods — determining the installation method for the current-carrying-capacity table
The guide on cable cross-section & current-carrying capacity
covers the base formula Iz = Itabel × f1 × f2 × f3. That article assumes
the correct Itabel value is already known. This article covers the
step that precedes it: how the physical way a cable is or will be
installed is translated into one of the reference methods from IEC
60364-5-52 — the key used to look up the correct table.
Why the installation method determines the table value
The same cable with the same cross-section has a different current- carrying capacity depending on how well the generated heat can be dissipated: a cable free in air cools better than the same cable embedded in a thermally insulated wall, and a cable in a cable tray alongside several other cables cools differently than a single cable on an open cable tray. IEC 60364-5-52 captures this by grouping installation methods into a limited set of reference methods, each with its own column in the current-carrying-capacity tables.
The main reference methods
| Method | Typical installation |
|---|---|
| A1 | Insulated conductors or single-core cable in conduit, in a thermally insulated wall |
| A2 | Multi-core cable in conduit, in a thermally insulated wall |
| B1 | Insulated conductors or single-core cable in conduit, on a wooden or masonry wall |
| B2 | Multi-core cable in conduit, on a wooden or masonry wall |
| C | Single-core or multi-core cable clipped directly to a wall or ceiling (or embedded in a wall), without conduit |
| D | Cable buried directly underground, or in an underground conduit |
| E | Multi-core cable free in air, or on a cable tray/ladder |
| F | Single-core cables free in air, touching each other |
As you go further down this table, heat dissipation generally improves and the permitted current-carrying capacity (at equal cross-section) tends to be higher — a cable free in air (method E/F) is usually allowed to carry noticeably more current than the same cable embedded in an insulated wall (method A1/A2).
From installation method to reference method
In practice, the reference method is not read off directly, but determined via a separate, more extensive example table (annex to IEC 60364-5-52) that links concrete installation situations — for example "cable in a tray on a perforated ladder" or "cable embedded in concrete" — to the corresponding reference method from the list above. This step is essential: choosing the wrong reference method directly leads to the wrong Itabel value, regardless of how carefully the correction factors f1/f2/f3 are applied afterwards.
Practical relevance
When sizing or checking a cable cross-section, identifying the correct reference method is the first step, before looking up Itabel and applying the correction factors: a cable calculated during design as method E (free air) but later actually embedded in an insulated wall (method A1/A2) has an assumed current-carrying capacity that is too high without recalculation.
Common mistakes
- Keeping the same reference method regardless of changes in the installation method — a cable that ends up embedded in an insulated wall or enclosed cable tray during execution requires a fresh look-up of the reference method.
- Assuming method E or F (free air) for an easier calculation while the cable is actually embedded in a wall or conduit — this results in an overly optimistic (too high) Itabel value.
- Applying the reference method of a single cable to a bundle without also applying the separate grouping correction factor (f2) from the cable cross-section guide — the reference method and the grouping correction are two separate steps that are both required.
- Ignoring the example table and estimating the reference method yourself based on a superficial resemblance — the official example table contains installation situations that are not always intuitively linked to the correct letter method.
Related
Further reading
- IEC 60502-1 / fabrikantrichtlijnenPulling cables — maximum pulling tension and minimum bend radius during installation
- §526.3 / IEC 60998Terminal connections compared — spring terminal versus screw terminal, and the accessibility requirement for junction boxes
- NEN-EN 1366-3Fire-resistant cable penetrations — NEN-EN 1366-3
- IEC 61439-6Busbar trunking systems (IEC 61439-6) — when to use them instead of cable
- IEC 60228Conductor classes IEC 60228 — class 1 through 6, and why the flexibility class determines the termination method
- NEN-EN 50525Decoding cable type designations — VOB, XVB, YMvK and the "as"/"mb" suffixes