NEN 1010 §523
Conductor cross-section vs. current
Aderdoorsnede vs. stroom
Also known as: doorsnede, aderdiameter, kabeldiameter, harmonischen, harmonics, thd, derde-harmonischen, 150-hz, neutral-overload, harmonic-neutral, nulgeleider-overbelasting
Conductor cross-section vs. current. YMvK 70 °C reference values: 2 or 3 current-carrying conductors, in air — 1.5 mm² = 16 A, 2.5 mm² = 20 A, 4 mm² = 25 A, 6 mm² = 32 A. Apply correction factors for temperature, bundling, and insulation type.
Practical example
Conductor cross-section vs. current: A 20 A kitchen circuit uses 2.5 mm² Cu; bundled with five others in one conduit, size often increases to 4 mm².
Common mistake
Cable cross-section vs. current Common mistake: Applying table values without correction factors in a cable tray with many circuits — actual current-carrying capacity is lower than stated.
See also
Related terms
In-depth guides
- → Wire Colors NL/EN/RU/UA/PL
- → §523 Cable cross-section & current-carrying capacity
- → §524 (IEC 60364-5-52) §524 — Minimum conductor cross-sections: the 1.5/0.5/0.75 mm² floor
- → §543.4 (IEC 60364-5-54) §543.4 — The PEN conductor: minimum cross-section and the switching prohibition
- → §712 Solar Power Systems (PV)
- → §542 / IEC 60364-5-54 Sizing an earth electrode — the calculation formulas for rod and plate electrodes
- → §542 Earth Electrodes — Foundation Earth Electrode, Rod and Ring Electrodes (§542)