Class 0 Equipment (Prohibited in the Netherlands)
Electrical equipment that relies solely on basic insulation for protection against electric shock, without a protective conductor (PE), without double/reinforced insulation (as in Class II) and without SELV/PELV supply (as in Class III) — in contrast to Classes I, II and III, each of which provides an explicit additional protective measure in case the basic insulation fails. With Class 0 equipment, a single insulation fault leads directly to a hazardous touch voltage on accessible conductive parts, with no second layer of protection. Although Class 0 is still listed in the classification of IEC 61140 internationally, its use in the Netherlands (and most other European countries) has been prohibited for newly manufactured and marketed equipment for decades; older Class 0 equipment still in use must be upgraded to at least Class I upon replacement.
Bij een NEN 3140-inspectie van oude apparatuur op een werkplaats treft de VP een verouderd klasse 0-apparaat aan zonder PE-aansluiting; dit wordt direct afgekeurd en vervangen door een klasse I- of klasse II-uitvoering, aangezien klasse 0 in Nederland niet meer is toegestaan.
Een apparaat zonder zichtbare PE-aansluiting aanmerken als 'klasse II' zonder het dubbele-vierkant-symbool te controleren — een apparaat zonder PE én zonder dat symbool kan in werkelijkheid een verboden klasse 0-uitvoering zijn, met een aanzienlijk hoger schokrisico dan een echte klasse II-uitvoering.
See also
- → §433 Overload protection (§433) — the coordination rule Ib ≤ In ≤ Iz and I₂ ≤ 1.45 Iz
- → §523 Cable cross-section & current-carrying capacity
- → §131 Protection Principles
- → §411.3.2 Automatic disconnection of supply (AUV)
- → §411.3.1 Earthing and earthing systems (TN, TT, IT)
- → Bijlage A (IEC 60364-4-41) Annex A — Basic protection against direct contact, IP2X and the jointed test finger