NEN-Hub
🔍
Examen

Calculation questions — short-circuit current & voltage drop

Available in: en, nl, pl, ru, ua
Updated: ≈ 3 min read

Calculation questions — short-circuit current & voltage drop

Two types of calculation questions recur on almost every NEN 1010/3140-related theory or practical exam: short-circuit current (needed to check whether a distribution board/circuit breaker can handle it) and voltage drop (needed to check whether equipment still functions within the permitted margin). This article covers both with a worked example.

Short-circuit current at the origin (Icc)

The maximum short-circuit current a transformer can deliver in the event of a direct short circuit on the secondary terminals:

Icc = In / %Ucc
  • In — rated secondary current of the transformer.
  • %Ucc — short-circuit voltage of the transformer, as a percentage of the rated voltage (typically 4–6% for distribution transformers, stated on the nameplate).

Worked example

Transformer 1000 kVA, 400 V, Ucc = 6%:

In = 1 000 000 / (1.732 × 400) ≈ 1 443 A
Icc = 1 443 / 0.06 ≈ 24 057 A ≈ 24 kA

This figure determines the minimum breaking capacity (kA) that the main circuit breaker or main distribution board must have — a circuit breaker with too low a breaking capacity can itself be damaged by this short-circuit current instead of switching off safely.

Ikmax versus Ikmin

Two different short-circuit currents are relevant for two different purposes:

Where calculatedWhat it is used for
IkmaxAt minimum cable impedance (short, thick, close to the source)Checking whether the breaking capacity of protective devices is sufficient.
IkminAt maximum cable impedance (long, thin, far from the source — often the end of the longest final circuit)Checking whether the protective device actually trips fast enough for a fault far away.

An installation checked only against Ikmax can still have a fault: at the end of a long, thin cable, the short-circuit current may be too low to make the circuit breaker trip within the required time (see §411, automatic disconnection of supply).

Voltage drop — the limits

NEN 1010 §525 (table 52.G.1) gives the maximum permitted voltage drop between the origin of the installation and any point of use:

  • 3% for lighting installations.
  • 5% for other uses (socket outlets, motors, general loads).

Note: older sources and rules of thumb sometimes mention higher percentages — for exams, use the official table values 3% / 5%.

Calculation formula

ΔU = (2 × ρ × L × I) / A
  • ρ — resistivity of copper (≈ 0.0175 Ω·mm²/m at 20°C).
  • L — length of the cable in metres (single direction).
  • I — load current in amperes.
  • A — cross-sectional area of the conductor in mm².
  • The factor 2 accounts for both the outgoing and return conductor (phase + neutral) — a common exam mistake is forgetting this factor.

Worked example

A socket outlet circuit, 25 m single length, 2.5 mm², load 10 A, 230 V:

ΔU = (2 × 0.0175 × 25 × 10) / 2.5 = 3.5 V
% = 3.5 / 230 × 100 ≈ 1.5%

This stays well within the 5% limit for other uses.

Common mistakes

  1. Forgetting the factor 2 in the voltage-drop formula — this gives a result that is half the actual voltage drop.
  2. Confusing Icc and Ikmin — Icc (at the origin) is almost always the highest current in the installation, Ikmin at the end of a long circuit the lowest; both are needed, for different checks.
  3. Using outdated voltage-drop percentages (e.g. 6%/8% from non-official rules of thumb) instead of the table values 3%/5% from §525.
  4. Confusing the %Ucc from the nameplate with the load factor — %Ucc is a fixed transformer property, not a percentage of the actual load.

Further reading

Related terms
Calculation questions — short-circuit current & voltage drop · NEN-Hub