Calculation questions — short-circuit current & voltage drop
Calculation questions — short-circuit current & voltage drop
Two types of calculation questions recur on almost every NEN 1010/3140-related theory or practical exam: short-circuit current (needed to check whether a distribution board/circuit breaker can handle it) and voltage drop (needed to check whether equipment still functions within the permitted margin). This article covers both with a worked example.
Short-circuit current at the origin (Icc)
The maximum short-circuit current a transformer can deliver in the event of a direct short circuit on the secondary terminals:
Icc = In / %Ucc
- In — rated secondary current of the transformer.
- %Ucc — short-circuit voltage of the transformer, as a percentage of the rated voltage (typically 4–6% for distribution transformers, stated on the nameplate).
Worked example
Transformer 1000 kVA, 400 V, Ucc = 6%:
In = 1 000 000 / (1.732 × 400) ≈ 1 443 A
Icc = 1 443 / 0.06 ≈ 24 057 A ≈ 24 kA
This figure determines the minimum breaking capacity (kA) that the main circuit breaker or main distribution board must have — a circuit breaker with too low a breaking capacity can itself be damaged by this short-circuit current instead of switching off safely.
Ikmax versus Ikmin
Two different short-circuit currents are relevant for two different purposes:
| Where calculated | What it is used for | |
|---|---|---|
| Ikmax | At minimum cable impedance (short, thick, close to the source) | Checking whether the breaking capacity of protective devices is sufficient. |
| Ikmin | At maximum cable impedance (long, thin, far from the source — often the end of the longest final circuit) | Checking whether the protective device actually trips fast enough for a fault far away. |
An installation checked only against Ikmax can still have a fault: at the end of a long, thin cable, the short-circuit current may be too low to make the circuit breaker trip within the required time (see §411, automatic disconnection of supply).
Voltage drop — the limits
NEN 1010 §525 (table 52.G.1) gives the maximum permitted voltage drop between the origin of the installation and any point of use:
- 3% for lighting installations.
- 5% for other uses (socket outlets, motors, general loads).
Note: older sources and rules of thumb sometimes mention higher percentages — for exams, use the official table values 3% / 5%.
Calculation formula
ΔU = (2 × ρ × L × I) / A
- ρ — resistivity of copper (≈ 0.0175 Ω·mm²/m at 20°C).
- L — length of the cable in metres (single direction).
- I — load current in amperes.
- A — cross-sectional area of the conductor in mm².
- The factor 2 accounts for both the outgoing and return conductor (phase + neutral) — a common exam mistake is forgetting this factor.
Worked example
A socket outlet circuit, 25 m single length, 2.5 mm², load 10 A, 230 V:
ΔU = (2 × 0.0175 × 25 × 10) / 2.5 = 3.5 V
% = 3.5 / 230 × 100 ≈ 1.5%
This stays well within the 5% limit for other uses.
Common mistakes
- Forgetting the factor 2 in the voltage-drop formula — this gives a result that is half the actual voltage drop.
- Confusing Icc and Ikmin — Icc (at the origin) is almost always the highest current in the installation, Ikmin at the end of a long circuit the lowest; both are needed, for different checks.
- Using outdated voltage-drop percentages (e.g. 6%/8% from non-official rules of thumb) instead of the table values 3%/5% from §525.
- Confusing the %Ucc from the nameplate with the load factor — %Ucc is a fixed transformer property, not a percentage of the actual load.
Related
Further reading
- §6.3Working De-energized — The 5 Steps (LOTO)
- ScopeNEN 3140 vs. NEN 3840 — where does low voltage stop?
- Examen40 NEN 3140 VP exam theory questions — with detailed answers
- §6.3Live working (WOS) — when is it allowed and with what protection?
- InspectieATEX & explosion-hazard zones — classification, inspection and relevance for horticulture
- §3.6Danger zone and approach zone — the three types of electrical work