NEN 1010 §701.415.2

Supplementary Equipotential Bonding (Wet Area)

Hulppotentiaalvereffening (natte ruimte)

A local, supplementary connection between all simultaneously accessible conductive parts within a bathroom, pool area or other wet room — including extraneous conductive parts such as water pipes, heating pipes and metal drains — applied in addition to the main equipotential bonding when the automatic disconnection time required by NEN 1010 cannot be guaranteed, or as an extra safety measure in zones 0/1/2. Its purpose is to limit the touch voltage between simultaneously accessible parts to a negligible level, regardless of whether an earth fault occurs. Unlike main equipotential bonding (carried out at the main intake), supplementary bonding is installed directly within the wet room itself.

Practical example

Bij de renovatie van een badkamer verbindt de installateur de metalen radiator, de koperen waterleidingen en de metalen douchegoot onderling en met de aardrail via een hulppotentiaalvereffeningsrail, ook al zijn alle groepen al door een 30 mA-aardlekschakelaar beveiligd.

Common mistake

Ervan uitgaan dat een 30 mA-aardlekschakelaar de hulppotentiaalvereffening in een badkamer overbodig maakt — de RCD beschermt tegen een te hoge aardfoutstroom, maar voorkomt niet dat er tussen twee gelijktijdig aanraakbare, niet-vereffende delen kortstondig een gevaarlijke aanraakspanning kan ontstaan.