IEC 60364-4-43 §434 / NEN 1010 §434

Backed-Up Protection (Cascading) for Inadequate Breaking Capacity

Achterwaartse bescherming (cascadebeveiliging) bij ontoereikend breekvermogen

An exception provision in IEC 60364-4-43 §434 (adopted into NEN 1010) that permits a circuit breaker with a breaking capacity lower than the actual prospective short-circuit current at that point to still be used, provided an upstream device (typically a fuse or circuit breaker with adequate breaking capacity) is installed immediately ahead of it and the let-through energy of that upstream device is demonstrably (via manufacturer data or type test) no higher than what the downstream circuit breaker and cabling can withstand thermally and dynamically. This is called 'backed-up protection' or 'cascading' and is not a substitute for a correctly rated device of its own, but an explicitly documented exception.

Practical example

Bij een subverdeler met een prospectieve kortsluitstroom van 10 kA maar installatieautomaten met Icn = 6 kA, past de installateur cascadebeveiliging toe met een bovenliggende 25A-zekering waarvan de fabrikant via een tabel bevestigt dat de doorgelaten energie binnen de grens van de automaten blijft, en documenteert dit expliciet in het installatiedossier.

Common mistake

Cascadebeveiliging toepassen zonder de fabrikantstabel of typetestverklaring te raadplegen, puur omdat 'de zekering er toch voor zit' — zonder aangetoonde compatibiliteit tussen de doorgelaten energie van de bovenliggende beveiliging en de weerstand van de installatieautomaat is er geen garantie dat de automaat een kortsluiting boven zijn eigen Icn daadwerkelijk overleeft.

See also

Beschikbaar in: English, Nederlands, Polski, Русский, Українська
Backed-Up Protection (Cascading) for Inadequate Breaking Capacity — dictionary · NEN-Hub