Shunt trip (MX) versus undervoltage release (MN) on circuit breakers — why one is fail-safe and the other is not
Shunt trip (MX) versus undervoltage release (MN) on circuit breakers — why one is fail-safe and the other is not
Circuit breakers (ACBs, MCCBs) are often fitted with an auxiliary coil that can force an opening remotely or via a safety circuit, independent of the breaker's own thermal and magnetic protection. IEC 60947-2 defines two mechanically similar but functionally opposite options for this: the shunt release (MX) and the undervoltage release (MN). In practice they are regularly confused, while the difference in fail-safe behaviour determines precisely whether an emergency-stop or safety circuit does what is expected of it.
Shunt release (MX release) — tripping via an active signal
The shunt release (MX release) opens the breaker when voltage is applied to the coil — via an impulse command (typically within a few tens of milliseconds, on the order of ≤20 ms) or via a maintained command. Opening is guaranteed when the coil is energised within the specified operating voltage range (typically up to roughly 0.7× rated control voltage and above); below the lower limit of that range, or with no voltage on the coil at all, nothing happens.
This means the shunt release is not fail-safe: if control voltage is lost — due to a broken supply cable, a failed auxiliary transformer or a dead control-voltage battery — the shunt release can no longer open the breaker, even if an emergency-stop signal is issued. The shunt release is therefore suitable for commands that are only relevant while control voltage is present (for example, a remotely commanded normal shutdown), but unsuitable as the sole means of opening for a safety function that must specifically work when control voltage is lost.
Undervoltage release (MN release) — tripping when voltage disappears
The undervoltage release (MN release) works the other way round: the coil must remain energised to keep the breaker closed. As soon as the voltage on the coil drops below a certain threshold, opening of the breaker is guaranteed — for an MN release, opening is typically guaranteed once coil voltage has fallen to roughly 0.35× rated control voltage or lower, while above roughly 0.7× of that rated voltage no opening occurs; between those two limits, behaviour is not guaranteed to be unambiguous. In addition, a de-energised MN coil prevents the breaker from being closed — manually or electrically — until coil voltage is again sufficiently high (closing is typically only guaranteed from roughly 0.85× rated voltage upward).
This makes the undervoltage release fail-safe: loss of control voltage — for whatever reason, including a broken cable or a blown fuse in the control circuit — automatically leads to the breaker opening, precisely the behaviour typically required of a safety circuit or emergency-stop function.
Note: the exact voltage thresholds (percentages of rated control voltage at which opening or closing is guaranteed or excluded) are laid down in IEC 60947-2 itself and must be verified per application against the current text of the standard and the rating plate of the specific breaker/coil, rather than assumed from rules of thumb alone.
MX and MN side by side on the same breaker
It is common for a circuit breaker to carry both an MX and an MN coil, each for a different purpose: the MX coil for a targeted, active remote command (for example from a PLC or control panel), and the MN coil as a fail-safe backstop that opens the breaker as soon as control voltage itself is lost — for example linked to an emergency-stop circuit that interrupts the MN coil's control voltage rather than sending a switching command. Confusing these two functions — for instance designing an emergency-stop circuit that energises an MX coil instead of interrupting the supply of an MN coil — undermines the fail-safe property the safety circuit was meant to provide.
Practical relevance
When assessing a switchgear installation during a NEN 3140 inspection (see also the guide on switching provisions and their classification and the guide on emergency-stop categories), it is important to check which type of coil is used for which function: an emergency-stop or safety circuit that depends on a shunt release stops working as soon as control voltage is lost, whereas that same loss of voltage on an undervoltage release actually produces the desired opening.
Common mistakes
- Relying on a shunt release (MX) for an emergency-stop or safety function without realising that it can no longer trip once control voltage itself is lost — fail-safe behaviour requires an undervoltage release (MN).
- Confusing MX and MN coils in drawings or specifications, since they look mechanically similar but behave in opposite ways.
- Assuming every undervoltage release trips within a few milliseconds at any voltage dip, without checking the exact voltage thresholds and time delays of the specific make against its rating plate and the standard.
- Fitting an undervoltage release without accounting for its closing behaviour: until coil voltage has sufficiently recovered, the breaker cannot be closed again either — a detail that can cause confusion on restart after a fault if it is not known in advance.
Related
Further reading
- Praktijk / IEC 60947-2Primary versus secondary injection testing of circuit-breakers — what each test method does and doesn't verify
- IEC 62271-100 / F-gas Reg. 2024/573Vacuum versus SF6 circuit breakers — arc-quenching principle, and why SF6 is being phased out
- Praktijk (ANSI 27/59)Undervoltage and overvoltage protection (ANSI 27/59) — why a generator or motor also needs protection against its own terminal voltage
- ANSI 62 (pole discrepancy)Pole discrepancy protection (ANSI 62PD) — when not all poles of a circuit breaker switch together
- Praktijk / IEC 62271-100Circuit breaker contact resistance measurement — the 1.2×Ru acceptance limit as a maintenance indicator
- IEC 60947-2Circuit-breaker trip settings — L, S, I and G in the LSI(G) protection curve