Is-limiter — pyrotechnic fault current limiter for bus-tie coupling with parallel transformers
Is-limiter — pyrotechnic fault current limiter for bus-tie coupling with parallel transformers
The [guide on Icw/Icm — short-time withstand current and making capacity](/guides/nen-3140/vermogensschakelaar-icw-icm-kortstondige-stroomsterkte-maakvermogen) covers how a circuit breaker must be rated for the prospective short-circuit current at its installation point. This article covers a specific situation where that prospective short-circuit current suddenly becomes higher than the existing switchgear can handle, because of a design change — and a device that solves that problem without replacing the switchgear itself: the Is-limiter.
The problem: bus-tie coupling raises the short-circuit current
In a low-voltage switchboard with two (or more) transformers, each feeding its own busbar section, a bus-tie breaker between the two busbar sections can be closed — for example, for operational reliability, so that if one transformer fails the other can supply both busbar sections. However, as long as the bus-tie is closed, both transformers jointly contribute to any short circuit on either busbar section: the prospective short-circuit current for a fault on busbar section A is then no longer just transformer A's contribution, but the sum of the contributions from both transformer A and transformer B via the closed tie.
See the [guide on short-circuit current calculation using the IEC 60909 impedance method](/guides/nen-1010/kortsluitstroomberekening-iec-60909-impedantiemethode) for how such a combined contribution is calculated. The practical consequence: the prospective short-circuit current with the bus-tie closed can be significantly — sometimes well above the short-circuit rating (Icw/Icm) of the existing circuit breakers, busbars, and other switchgear — higher than the short-circuit current of either transformer alone.
The conventional solution and why it isn't always practical
The conventional solution is to replace the entire switchgear — busbars, circuit breakers, protection relays — with equipment rated for a higher short-circuit capacity that can handle the full combined short-circuit current. In an existing installation where the bus-tie must only later be kept permanently closed (for example after a change in operating philosophy, or after an expansion with a second transformer), this is a costly and time-consuming intervention that often requires a prolonged shutdown of the entire switchboard.
How an Is-limiter solves this: interrupting before the first current peak
An Is-limiter is a pyrotechnic switching element placed specifically in the bus-tie connection itself, which, upon detecting a short-circuit current that exceeds a preset pickup value, physically interrupts the bus-tie connection within a few milliseconds — well before the first current peak (the first peak of the asymmetrical short-circuit current) is reached — by explosively severing a conductor and extinguishing the resulting arc almost instantly in a dedicated quenching medium.
Because the interruption takes place before the short-circuit current reaches its peak value, the rest of the installation — the existing busbars and switchgear on either side of the coupling — "sees" a short-circuit current that remains limited to roughly the level of a single transformer, instead of the full, unimpeded sum of both transformers. As a result, the existing switchgear does not need to be over-rated for the combined short-circuit current, even though the bus-tie remains closed during normal operation.
Note: an Is-limiter is fundamentally different from a circuit breaker or fuse — it is designed to limit the rise of the current itself before the peak value is reached, not to simply trip after a fault like a regular protective device. This makes it suitable as an additional current-limiting device in the bus-tie connection, not as a replacement for the regular discriminative protection of the outgoing feeders.
The key limitation: single-use operation
The pyrotechnic operating principle of an Is-limiter means that the device is physically consumed upon activation and must be replaced before the bus-tie can be put back into service — unlike a circuit breaker, which can simply be reset and re-closed after the fault has been cleared. This is a deliberate design trade-off: the Is-limiter is expected to operate only rarely (only during an actual short circuit with the bus-tie closed), and the cost of occasional replacement often outweighs the savings from not having to replace the full switchgear.
Practical relevance
When assessing a switchboard with two or more transformers operated in parallel and a bus-tie that must remain permanently closed, an Is-limiter is an option worth considering when the combined prospective short-circuit current exceeds the short-circuit rating of the existing switchgear — especially in an existing installation where full replacement of the switchgear would be disproportionately costly or operationally infeasible. When applying it, verify that the pickup value of the Is-limiter is correctly matched both to the normal operating current through the bus-tie (no unwanted activation during normal load switching) and to the actual short-circuit contribution of the second transformer.
Common mistakes
- Permanently closing a bus-tie after an expansion with a second transformer without recalculating the combined prospective short-circuit current, unknowingly loading the existing switchgear beyond its short-circuit rating.
- Treating an Is-limiter as a replacement for regular discriminative protection of the outgoing feeders — the Is-limiter specifically limits the combined contribution via the bus-tie during a busbar fault, not the normal discrimination between feeders.
- Not keeping a replacement unit in stock, so the bus-tie stays out of service longer than necessary after an activation.
- Setting the pickup value incorrectly relative to the normal operating current through the tie, causing an unwanted activation (and thus unnecessary replacement cost) during a normal, non-faulted load current.
Related
Further reading
- IEC 60076-1 / IEC 60599Buchholz relay (gas relay) — two-stage gas protection for oil-filled power transformers
- IEC 60076-2 / PraktijkOil and winding temperature indicators (OTI/WTI) — thermal monitoring of an oil-filled power transformer
- ANSI 50N/51N ground-fault OCGround-fault overcurrent protection (ANSI 50N/51N) — residual connection versus core-balance CT
- ANSI 51VVoltage-dependent overcurrent protection (ANSI 51V) — voltage-restrained versus voltage-controlled on a generator
- ANSI 49 / IEC 60255-149Thermal replica protection (ANSI 49) — thermal model for motor and transformer
- Praktijk (ANSI 79)Automatic reclosing (ANSI 79) — why an overhead MV line automatically closes back in after tripping