NEN-Hub
🔍
IEC 60909-0

X/R Ratio (Fault Current Asymmetry)

X/R-verhouding (asymmetrie van de kortsluitstroom)

The ratio between the reactance (X) and resistance (R) of the network up to a fault point, which determines how pronounced the DC component (the asymmetrical, initially elevated peak) of the fault current is relative to the eventual symmetrical (steady-state) fault current. A high X/R ratio (typically close to large transformers or generators, where reactance dominates) results in a more slowly decaying DC component and therefore a higher peak value (making current, ip) relative to the effective symmetrical current, while a low X/R ratio (further into the network, where resistance becomes relatively more significant) gives a faster-decaying, less asymmetrical current. The X/R ratio is essential when determining the required making capacity (Icm) of circuit breakers per IEC 60909-0/IEC 62271-100, alongside the already familiar breaking capacity.

Practical example

Bij de selectie van een vermogensschakelaar direct achter een grote vermogenstransformator berekent de ontwerper de X/R-verhouding op dat punt om te controleren of het opgegeven maakvermogen (Icm) van de schakelaar toereikend is voor de verhoogde piekstroom door de trage asymmetrische demping.

Common mistake

Bij de keuze van een vermogensschakelaar alleen naar het symmetrische breekvermogen (Icu/Ics) kijken en de X/R-verhouding van het net negeren — dicht bij een grote transformator kan de werkelijke piekstroom (Icm) door een hoge X/R-verhouding aanzienlijk hoger uitvallen dan de symmetrische waarde alleen doet vermoeden.

See also