⚑NEN-Hub
πŸ”
Β§9

Fuse systems β€” Diazed, Neozed and NH

Available in: en, nl, pl, ru, ua
Norm edition: NEN 3140:2011+A3:2019

This page has not yet been technically reviewed by a qualified person. Always check the current standard and your own appointment (aanwijzing); this is not a substitute for NEN 3140 or NEN 1010.

Found a mistake? Tell us

Updated: β‰ˆ 5 min read

Fuse systems β€” Diazed, Neozed and NH

Besides circuit breakers (MCBs, see the B/C/D characteristics), you'll still regularly encounter fuse systems in older and industrial installations. Three systems dominate Dutch practice.

Diazed (D-system)

The classic screw-cartridge system, recognisable by the porcelain fuse holder with screw thread.

  • Adapter ring (passchroef): a ring fitted in front of the fuse link that physically prevents a cartridge with a higher current rating than intended from being inserted β€” the adapter ring is itself the first barrier against an incorrect replacement, independent of the fuse link.
  • Fuse-holder numbering: the common designation "25/16" means a fuse holder rated up to 25 A, into which β€” via the adapter ring β€” a cartridge of at most 16 A is permitted.

Diazed cartridge colour code:

Diazed cartridge colour code, 2 A to 63 A

CurrentColour
2 APink
4 ABrown
6 AGreen
10 ARed
16 AGrey
20 ABlue
25 AYellow
35 ABlack
50 AWhite
63 ACopper

Neozed (D0 system)

The successor to Diazed: more compact, with no separate adapter ring needed because the cartridge itself has a diameter/shape tied to its current rating that physically prevents incorrect insertion. Recognisable by the designation D01 (up to 16 A) and D02 (up to 63 A); for higher currents there's also D03 (up to 100 A).

NH knife-fuses (fuse-switch disconnector)

For higher power ratings: flat cartridges with knife-shaped contacts, mounted in a fuse-switch disconnector (also called a knife switch). Common in main distribution boards and industrial installations up to several hundred amps. An NH fuse link is always replaced with a dedicated fuse-puller β€” the fuse-puller tongs β€” (never bare-handed) and preferably with the circuit de-energised, after the load has been removed (see also the load-break switch / isolator rule).

Because removing a knife fuse carries a risk of arc flash, a mandatory PPE set applies: insulating gloves class 00 (500 V) or class 0 (1000 V), a face shield/visor, flame-retardant clothing free of synthetic fibres, and safety footwear S3 β€” in addition to the fuse-puller tongs themselves.

gG versus aM β€” the second letter matters

Every fuse link carries, alongside its current rating, a letter code describing its tripping behaviour:

  • gG ("general purpose") β€” protects against both overload and short-circuit, suitable for general cable and line protection.
  • aM ("accompagnement Moteur", motor protection) β€” protects exclusively against short-circuit and is deliberately slow on overload, so that a motor's inrush current doesn't cause unnecessary blowing. An aM fuse link must always be combined with a separate thermal motor protection device (motor-protection switch) for overload protection β€” an aM cartridge alone does not protect the motor winding against prolonged overload.

Never confuse the two: an aM fuse link on a cable without additional overload protection lets an overload continue unchecked far above the rated current.

A motor-protection switch (MBS) is a separate switching device, specifically designed to protect the motor winding against overload β€” precisely the gap an aM fuse link deliberately leaves open (see above). An MBS combines two protections in a single device:

  • Thermal element β€” an adjustable, hand-calibrated dial that you set exactly to the rated current In on the nameplate of the connected motor. On overload, the MBS trips within a time that belongs to its trip class.
  • Magnetic element β€” a fixed, fast trip on short-circuit, comparable to the magnetic trip of a circuit breaker.

Trip classes (EN/IEC 60947-4-1) β€” the range within which the MBS must trip at 7.2 Γ— Ie, starting from cold (class 10A shares the same maximum time as class 10, but has a lower minimum time β€” intended for applications that need a faster response without shortening the maximum trip time):

ClassTrip time at 7.2 Γ— Ie (min–max)Typical application
10A2–10 sVery light starting, fast response wanted
104–10 sStandard motors, short start-up
206–20 sHeavier starting (pumps, fans)
309–30 sHeavy starting, large moments of inertia

An MBS is almost always combined into a direct-on-line starter (DOL starter): aM fuses or a circuit breaker for short-circuit protection, the MBS for thermal overload protection, and a contactor to actually switch the motor on and off. In the exam and in practice you'll come across brands such as Eaton (PKZM0 series) and Hager (K series) for this β€” the principle (thermal + magnetic, separate from the fuse) is the same for every brand.

Most common mistake: setting the MBS dial to the current rating of the fuse or cable instead of to the motor's In. An MBS set too high doesn't protect the winding against overload; an MBS set too low won't even let the motor start. Always set the MBS based on the nameplate of the motor actually connected β€” see also replacing a motor, where this setting must be checked again as soon as the motor is replaced.

Comparison with circuit breakers

Just as with replacing a B16 with a D16 (see the B/C/D characteristics), the same applies to fuse systems: the current rating and tripping behaviour (gG/aM) belong to the circuit's design calculation. Replacing a cartridge with a higher rating or a different type without recalculating the cable protection and disconnection time is a modification of the installation, not a simple maintenance action.

Further reading

Related terms
Fuse systems β€” Diazed, Neozed and NH Β· NEN-Hub