SPD Cascading and Energy Coordination (Type 1/2/3)
The principle that when several surge protective devices (SPDs) of different types are installed in series in an installation — for example a Type 1 at the main incoming supply, a Type 2 in the distribution board and a Type 3 close to sensitive equipment — they must be mutually matched (coordinated) so that the residual energy let through by the upstream stage does not exceed what the downstream SPD can safely handle. Without correct energy coordination, typically demonstrated through manufacturer coordination tables or a minimum cable length between stages, an SPD closer to the load can become overloaded while the upstream SPD has not yet operated, resulting in failure or even fire of the downstream device. NEN 1010 requires demonstrable coordination when cascading SPDs, not merely the presence of multiple stages as such.
Bij een nieuwbouwproject met een Type 1-SPD op de hoofdaansluiting en een Type 2-SPD in de groepenkast controleert de installateur in de fabrikantendocumentatie of de gecombineerde toepassing gecoördineerd is verklaard, of dat een minimale kabellengte tussen beide SPD's moet worden aangehouden.
Ervan uitgaan dat het plaatsen van een Type 1- en een Type 2-SPD in dezelfde installatie automatisch een goede beveiliging oplevert, zonder te controleren of beide onderling energetisch gecoördineerd zijn volgens de fabrikantspecificaties.
See also
- → §443 / IEC 61643-11 / IEC 61643-12 Energy coordination between Type 1 and Type 2 SPDs — the '10-metre rule' and decoupling impedance
- → §433 Overload protection (§433) — the coordination rule Ib ≤ In ≤ Iz and I₂ ≤ 1.45 Iz
- → §8-1 / IEC 60364-8-1 NEN 1010 Part 8-1 — Energy efficiency of electrical installations (IEC 60364-8-1)
- → IEC 60364-5-53 RCD selectivity — Type S and cascading residual current devices
- → IEC 60755 RCD types AC/A/F/B — classification and selection by load type (IEC 60755)
- → §411 Protective earthing (PE)