NEN-Hub
🔍
NEN-EN 1838

Emergency Lighting Autonomy Time

Autonomietijd noodverlichting

The length of time an emergency lighting installation (escape-route lighting) must keep functioning on its own battery power after the normal supply fails, before occupants can be expected to have left the building or the normal supply is restored. NEN-EN 1838 and building regulations typically require a minimum of 1 hour for standard escape routes, rising to 3 hours for buildings where evacuation takes longer or is not complete (e.g. healthcare facilities, large public buildings). Autonomy time is a separate requirement from the switch-on time (50% light within 5 s, 100% within 60 s) and must be tested separately, e.g. by fully discharging the battery during a periodic test.

Practical example

Bij de periodieke inspectie van een verzorgingstehuis test de inspecteur niet alleen of de armaturen binnen 5 seconden aanslaan, maar laat hij de accu's ook een volledige cyclus van 3 uur ontladen om te bevestigen dat de voorgeschreven autonomietijd nog wordt gehaald.

Common mistake

Bij een periodieke NEN 3140-inspectie alleen controleren of de noodverlichting bij een korte netonderbreking aanslaat, zonder de volledige autonomietijd te testen — een verouderde accu kan de inschakeltest doorstaan maar na bijvoorbeeld 20 minuten al uitvallen, ruim binnen de vereiste periode.

See also

Beschikbaar in: English, Nederlands, Polski, Русский, Українська
Emergency Lighting Autonomy Time — dictionary · NEN-Hub