Intentional Microgrid Island Operation
The deliberate, planned state in which a microgrid (a local assembly of generation, storage and load, such as an industrial estate with PV, battery storage and a CHP installation) electrically disconnects from the public grid and continues to supply itself independently, with its own voltage and frequency control — a state explicitly different from the unwanted, unintentional islanding that anti-islanding protection of PV inverters is specifically designed to prevent. To operate safely and stably in intentional island mode, at least one source within the microgrid must be able to act as a 'grid-forming' element (actively regulating voltage and frequency instead of merely injecting current onto an already-present grid voltage, as most PV inverters do), and the transition to and from grid-connected operation must follow a defined switching sequence and synchronisation check to prevent damaging inrush currents or phase mismatches. Applications are found mainly at critical facilities (hospitals, data centres) and in grid-congestion areas where island operation can temporarily provide relief, but protection settings, earthing philosophy (the star point may need to be locally re-formed during island operation) and selectivity must be calculated separately for both operating states.
Bij een geplande netonderbreking voor onderhoud schakelt het energiemanagementsysteem van een ziekenhuiscomplex het lokale microgrid met noodstroomaggregaten en batterijopslag bewust over naar intentioneel eilandbedrijf, waarbij één aggregaat de rol van grid-forming bron op zich neemt.
Aannemen dat een net met alleen grid-following PV-omvormers (zonder grid-forming bron of batterijomvormer) in staat is tot stabiel intentioneel eilandbedrijf, terwijl deze omvormers juist afhankelijk zijn van een reeds aanwezige netspanning om te kunnen synchroniseren en injecteren.
See also
- → IEEE 1188 (VRLA) Stationary battery — capacity test and internal-resistance (ohmic) test (IEEE 1188)
- → IEC 62485-2 Ventilation of stationary battery rooms (UPS/telecom) — IEC 62485-2
- → Praktijk (UPS N+1 parallel) UPS parallel operation — N+1 redundancy and circulating current between modules
- → IEC 61800-5-2 Safely switching off frequency inverters — Safe Torque Off (IEC 61800-5-2)
- → IEC 61230 (aardingsset) Earthing and short-circuiting sets — periodic testing per IEC 61230
- → Inspectie Testing the RCD — trip time and residual current (NEN-EN-IEC 61557-6)