NEN 1010 §612.6
Fault-loop impedance
Lusimpedantie (Zs)
Also known as: lus, lusimpedantie, zs, loop-impedance, earth-loop-impedance
Loop impedance (Zs). Impedance of the fault loop phase → PE → source. Determines prospective short-circuit current Is and whether the overcurrent protection trips within the required time. Measure at each type test and after every change.
Practical example
Loop impedance (Zs): At a remote final circuit, Zs measures 1.8 Ω; with a 16 A Type B MCB, tripping time is excessive, requiring cable upsizing.
Common mistake
Loop impedance (Zs). Common mistake: Calculating Zs solely from cable length and cross-section without actual measurement—loose connections or corrosion in the path increase the actual impedance.