Cross-Bonding Cable Screen — Suppressing Circulating Currents (HV/MV)

Cross-bonding kabelscherm — onderdrukking circulerende stromen (hoog-/middenspanning)

An earthing technique for the metallic screens of long single-core high- or medium-voltage cables (IEC 60840, recommended by CIGRE TB 283) in which the screen is not solidly earthed at both ends (which over long runs would generate large circulating currents in the screen due to the voltage induced by the core conductor), but is instead divided into numbered sections with cross-transposition of the screen connections at each section joint, so that the voltages induced in each section largely cancel out over the full cable length. Only the ends of the entire cross-bonded run are solidly earthed; the intermediate screen sections are protected against transient overvoltages by sheath voltage limiters (SVLs).

Practical example

Bij een 3 km lange 150kV-kabelverbinding verdeelt de netbeheerder het traject in drie gelijke cross-bonded secties met SVL's op de tussenliggende schermverbindingen, in plaats van het scherm eenzijdig te aarden, om zowel circulerende stromen als een te hoge schermspanning bij eenzijdige aarding te vermijden.

Common mistake

Bij een lange enkeladerige hoogspanningskabel het scherm 'voor de zekerheid' aan beide uiteinden direct te aarden zonder cross-bonding toe te passen — dit voorkomt weliswaar schermoverspanning, maar wekt juist grote circulerende stromen in het scherm op die extra verliezen en opwarming veroorzaken, wat cross-bonding nu net beoogt te voorkomen.

See also

Beschikbaar in: English, Nederlands, Polski, Русский, Українська
Cross-Bonding Cable Screen — Suppressing Circulating Currents (HV/MV) — dictionary · NEN-Hub