NEN-Hub
🔍
NEN-EN-ISO 8528-4

Generator Synchronisation (Grid-Parallel Connection)

Generatorsynchronisatie (parallelschakeling met net)

The process by which a generator, before the tie breaker to an already energised network is closed, is matched as precisely as possible to that network in terms of voltage, frequency, phase sequence, and phase angle, in order to prevent damaging current surges or mechanical shocks upon closing. A synchronisation relay or unit continuously monitors these quantities and only permits closing once all values fall within the permitted tolerances; if exceeded, the relay blocks closure. Faulty synchronisation — for example closing with an excessive phase-angle deviation — can result in extremely high inrush currents capable of seriously damaging both the generator and the rest of the installation.

Practical example

Bij een testrun van een noodstroomaggregaat met automatische netparallelfunctie controleert de inspecteur of het synchronisatierelais de koppeling pas vrijgeeft nadat spanning, frequentie en fasehoek van generator en net binnen de ingestelde toleranties overeenkomen.

Common mistake

De synchronisatiebeveiliging tijdens een handmatige noodprocedure overbruggen om een aggregaat 'sneller' op het net te krijgen — dit omzeilt juist de bescherming tegen de gevaarlijkste faalmodus van parallelschakeling en kan zowel de generator als aangesloten apparatuur direct beschadigen.