NEN 1010 §311
Diversity factor (simultaneity)
Gelijktijdigheidsfactor
A factor (< 1) applied to the summed rated load of circuits because not all loads run at full power at once. Used to size the main feeder, main switch and connection capacity. NEN 1010 §311 gives reference values per occupancy (dwelling, office, industry).
Practical example
Coincidence factor: Ten 16 A circuits do not yield 160 A main current; with a coincidence factor of 0.5, calculate ~80 A and select the main fuse accordingly.
Common mistake
Coincidence factor Common mistake: Sizing the main fuse on the sum of nominal values of all circuits without the coincidence factor — resulting in an unnecessarily heavy and expensive main connection.
See also
Related terms
- Voltage drop
- Conductor cross-section vs. current
- Main switch / isolator
- Isolation transformer (electrical separation)
- Conductor Short-Circuit Withstand (Adiabatic Formula, k-Factor)
- PEN conductor
- DC Arc-Fault Detection Device (DC AFDD) for PV Installations
- Confined Conductive Locations with Restricted Movement
- Temporary Installation — Exhibitions, Shows and Fairground Attractions (§711)
In-depth guides
- → NEN-EN-IEC 61439-1/-2 (3e editie) Group rated current replaces the simultaneity factor — sizing the main cable and distribution board
- → §704 Temporary installations on construction and demolition sites
- → §740 Temporary installations at fairgrounds and events (§740) — mandatory 30mA RCD
- → NEN 1010 (e-bike-laadpunt) Charging points for e-bikes and scooters in shared storage — installation requirements and fire safety
- → IEC 60479-1 (DC) DC microgrids in buildings — earthing choice and the polarity trade-off on a DC busbar
- → IEC 62955 / NEN 1010 §722 RDC-DD — detecting smooth 6 mA DC fault current at charge points
Beschikbaar in: English, Nederlands, Polski, Русский, Українська