IEC 60071-1

Earth Fault Factor (IT System)

Aardfoutfactor (IT-stelsel)

The ratio between the phase-to-earth voltage on the healthy phases during a single earth fault in an unearthed (or high-impedance earthed) IT system, and the normal phase-to-earth voltage without a fault. Because the star point in an IT system is not solidly earthed, a first earth fault does not interrupt supply, but the voltage on the two healthy phases relative to earth rises: in an IT system without a star-point impedance, this factor can theoretically reach up to √3 (approximately 1.73), corresponding to the full line-to-line voltage. This elevated voltage must be accounted for in the design when coordinating insulation for cables, switchgear and surge protection devices connected to the network, since this equipment must therefore permanently withstand the elevated voltage for as long as the first fault remains undetected, underscoring the importance of timely insulation monitoring (IMD).

Practical example

Bij het ontwerp van een IT-gevoede OK-groep in een ziekenhuis dimensioneert de ontwerper de isolatiewaarden van de kabels op een aardfoutfactor van √3, zodat de installatie een langdurige eerste aardfout zonder isolatiedoorslag kan doorstaan totdat de IMD een storing meldt.

Common mistake

Bij de isolatiecoördinatie van een IT-net uitgaan van de normale fase-aardespanning zonder rekening te houden met de verhoogde spanning tijdens een eerste aardfout — hierdoor kan materieel dat net buiten de eerste-foutperiode nog in bedrijf is, alsnog een isolatiedoorslag oplopen.