§705 — Horticultural Enterprises and Greenhouses
Special room with elevated risks: moisture, mechanical damage, fire hazard during CO₂ fertilization and assimilation lighting.
Requirements
- Minimum IP55 for switching and distribution equipment in the greenhouse itself (§705.512).
- IP67 in areas where regular spraying or sweeping takes place.
- 30 mA residual current device (RCD) on all final circuits for portable equipment.
- Separate 300 mA RCD for fire protection on circuits for lighting > 32 A.
- Main equipotential bonding on metal gutters, walkways, and CO₂ pipes.
Practice in Westland greenhouses
- Assimilation luminaires (HPS 600/1000 W or LED): keep in mind that HF interference can blind RCD type A — type F or B is recommended.
- Pt1000 sensors for climate control: see Practical → Pt1000 3-wire connection.
- Many inverters on one RCD → cumulative leakage current check mandatory.
- Priva, Hoogendoorn, Hortimax — note proprietary connectors, but the 1010 requirements apply in full.
Further reading
Related guides
- §705Livestock buildings and agricultural premises (§705) — earth potential in livestock-accessible zones
- §705 / IEC 60335-2-76Electric fence energizers on agricultural premises (§705) — why the energizer itself, not just the wiring, is part of the installation assessment
- Netcode ElektriciteitGrid congestion, peak shaving & battery storage for business
- §704Temporary installations on construction and demolition sites
- §444 (IEC 60364-4-44)§444 — Measures against electromagnetic disturbances (EMC) in building installations
- §701Bathrooms and Shower Rooms