NEN-Hub
🔍
Praktijk (ANSI 25)

Synchronizing check (ANSI 25) — why a breaker may only close once voltage, frequency, and phase angle match

Available in: en, nl, pl, ru, ua
Updated: ≈ 5 min read

Synchronizing check (ANSI 25) — why a breaker may only close once voltage, frequency, and phase angle match

The guide on generator grid connection and the guide on reverse-power protection (ANSI 32) cover situations where a generator (or a second grid) runs in parallel with an existing grid. This article covers the protection function that supervises the moment of paralleling itself: synchronizing check, also called a sync-check relay, designated by ANSI code 25.

Why an incorrect paralleling operation is damaging

When a breaker connects two already-energized sources — for example a generator to the grid, or two sections of a switchboard that are each already live — both sources must, at the moment of closing, sufficiently match each other in voltage magnitude, frequency, and phase angle. If these deviate too much, closing the breaker creates a sudden, large equalizing current between the two sources: in the worst case — closing with a phase-angle difference close to 180° — the resulting inrush current and the associated torque on the generator shaft can be comparable to that of a short circuit close to the terminals, with the risk of mechanical damage to the shaft, the coupling, and the windings.

What a synchronizing-check relay actually monitors

A 25 relay continuously compares the voltages on both sides of the breaker to be closed on three quantities, and only issues a permissive to close once all three are within their set limits:

  • Voltage difference: the difference in magnitude between the two sources must lie within a narrow margin — in practice typically on the order of a few percent of nominal voltage.
  • Frequency difference (slip): the permissible frequency difference between the two sources is typically very small when coupling two stiff grids, but may be wider when a generator is being manually or automatically synchronized to the grid, so that the phase angle progresses gradually and in a controlled manner rather than fluctuating rapidly.
  • Phase-angle difference: most applications limit the permissible phase-angle difference at the moment of closing to a small margin, typically on the order of a few degrees up to roughly 10° at most, so that the residual equalizing current at closing stays limited.

Only once all three conditions are simultaneously within their set limits does the 25 relay release the close command — either as the last check before a manual closing by the operator, or as a permissive signal for an automatic synchronizer that actively adjusts the generator's speed and excitation to reach the synchronizing point.

Sync-check versus active synchronization

It is important to distinguish between two related but different functions:

  • A sync-check relay (25) is purely a supervisory function: it passively assesses whether the synchronizing conditions are met and only issues a permissive, without actively adjusting anything itself. It is often applied as an independent, final check alongside a manual closing or alongside a separate automatic synchronizing system.
  • An automatic synchronizer goes a step further: it actively adjusts the speed (and thus the frequency) and sometimes the excitation (and thus the voltage) of the generator to reach the synchronizing conditions, and then itself issues the close command at the right moment.

In many installations both functions work together: the automatic synchronizer actively drives the machine toward the synchronizing point, while an independent sync-check relay acts as a final, redundant check that still blocks the close command if the conditions are, for whatever reason, not actually met.

Note: the exact limits for voltage difference, slip, and phase angle follow from the system study of the specific generator or coupling and from the grid operator's requirements; this article covers the principle, not a ready-made setting table for every application.

Practical relevance

When commissioning a generator that must synchronize to the grid, it is important to verify that the sync-check relay is actually wired in series with the breaker's close command — a synchronizer that actively regulates but whose close command is not actually supervised by an independent sync-check relay lacks the final, independent protection layer against an incorrect paralleling operation caused by a fault in the synchronizer itself.

Common mistakes

  1. Relying solely on the automatic synchronizer, without an independent sync-check relay as a final check — a fault in the synchronizer itself then remains unsupervised.
  2. Setting overly wide phase-angle or slip limits to speed up synchronizing — this increases the risk of a noticeable inrush current and torque at closing.
  3. Applying the same sync-check setting to a coupling between two stiff grids as to a generator-to-grid synchronization — both situations typically require a different sensitivity to slip.
  4. Not reviewing the sync-check relay after a change in generator or grid configuration — a system change can shift the acceptable margins for voltage, slip, and phase angle.

Further reading

Related terms
Synchronizing check (ANSI 25) — why a breaker may only close once voltage, frequency, and phase angle match · NEN-Hub