NEN-Hub
🔍
IEC TS 62478 (PD, UHF/TEV)

Partial discharge in MV switchgear — detection with UHF and TEV sensors

Available in: en, nl, pl, ru, ua
Updated: ≈ 4 min read

Partial discharge in MV switchgear — detection with UHF and TEV sensors

The guide on partial-discharge measurement and tan-delta on MV cables covers PD detection via the classic, charge-based measurement per IEC 60270 on a de-energised cable. This article covers a related but substantially different application: detecting partial discharge (PD) in an energised medium-voltage switchgear assembly, using UHF (ultra-high-frequency) and TEV (transient earth voltage) sensors, as described in IEC TS 62478 ("High voltage test techniques — Measurement of partial discharges by electromagnetic and acoustic methods").

Why a different measurement technique is needed for switchgear

The classic IEC 60270 charge measurement requires a controlled, de-energised test setup with a coupling capacitor directly on the conductor under test — suitable for a disconnected cable, but not practical for a complete, energised switchgear assembly with multiple panels, where de-energising for every periodic check would mean a significant service interruption. UHF and TEV detection instead measure the by-products of a PD pulse — an electromagnetic wave (UHF) or a brief voltage transient on the earthed enclosure (TEV) — and can do so while the assembly stays in service.

Operating principle: two different signals from the same source

  • UHF detection: a PD pulse lasts only a few nanoseconds and radiates electromagnetic energy up into the gigahertz range. A UHF sensor — often a built-in window antenna in gas-insulated switchgear (GIS), or an external sensor on air-insulated equipment — picks up this wave. Because the metal enclosure of a GIS largely shields the signal from external noise, UHF detection on GIS is particularly sensitive and low in interference.
  • TEV detection: in air-insulated metal-clad switchgear, an internal PD pulse causes a brief voltage transient on the inside of the earthed metal enclosure, which also manifests as a measurable TEV pulse on the outside through small openings (seams, ventilation grilles, cable entries). A TEV sensor is simply held against or mounted on the outside of the enclosure, without the assembly having to be opened.

Note: neither technique produces a picocoulomb-calibrated charge value the way the IEC 60270 method does. UHF and TEV measurements are primarily qualitative and comparative: they detect the presence and relative intensity of PD activity and are therefore mainly suited to trending and triage, not to an absolute conformity assessment against a pC limit.

Practical use

  • Periodic walk-round with a handheld UHF/TEV instrument across all panels of a switchgear assembly, comparing the measured signal levels with each other: a panel with a clearly higher level than the other, comparable panels points to local PD activity that warrants further investigation.
  • Permanently mounted sensors with data logging on critical switchgear, similar to the use of a power-quality datalogger, flagging a gradually rising trend before it leads to a breakdown.
  • Combination with acoustic or corona detection: on air-insulated equipment, TEV detection can be combined with UV-camera and ultrasonic corona detection of external corona phenomena, while UHF mainly detects internal PD in a closed enclosure that a UV camera cannot see.
  • Localisation within a switchgear assembly: by comparing signal strength at multiple measurement points around the same panel (for example with several TEV sensors or a time-difference analysis between UHF sensors), the likely PD source within the panel can be narrowed down further, as a supplement to — not a replacement for — a targeted offline measurement if there is doubt.

Practical relevance

During the periodic inspection of a medium-voltage switchgear assembly under NEN 3140, non-invasive UHF/TEV PD detection is a valuable addition to thermographic inspection: where thermography reveals heat generation from an elevated contact resistance, PD detection reveals incipient insulation degradation that at that point still causes no measurable temperature rise — often well before a breakdown occurs.

Common mistakes

  1. Interpreting a measured UHF or TEV signal level as a calibrated pC value, while both techniques are primarily qualitative and comparative in nature.
  2. Not recording a baseline measurement on a known PD-free installation, so a later measurement cannot be assessed against a known starting value.
  3. Using UHF detection on air-insulated equipment without metal shielding, where sensitivity to external electromagnetic noise is considerably higher than on GIS.
  4. Ignoring an elevated PD signal because the installation does not yet show a noticeable temperature rise on thermographic inspection, while PD activity signals an earlier stage of insulation degradation than a thermal effect.

Further reading

Related terms
Partial discharge in MV switchgear — detection with UHF and TEV sensors · NEN-Hub