Symmetrical components — asymmetric fault analysis per Fortescue
Symmetrical components — asymmetric fault analysis per Fortescue
The guide on short-circuit current calculation per IEC 60909-0 covers the equivalent-voltage-source method for calculating Ik'' — but at its core, that method in its basic form applies directly to one specific case: the symmetrical three-phase fault (all three phases short-circuited simultaneously), where the network remains fully balanced after the fault occurs. The vast majority of real faults on a network are, however, asymmetric: a single line-to-ground fault, a fault between two phases, or a fault between two phases and earth. For those cases a simple single-phase equivalent circuit is not enough — this requires the method of symmetrical components, developed by Charles Fortescue (1918).
Fortescue's theorem
Fortescue showed that any arbitrary unbalanced (asymmetric) three-phase phasor system can be mathematically decomposed into the sum of three symmetrical sub-systems:
- Positive-sequence component (1) — three phasors of equal magnitude, 120° apart, in the same phase sequence as the original, healthy network.
- Negative-sequence component (2) — three phasors of equal magnitude, also 120° apart, but in the reverse phase sequence.
- Zero-sequence component (0) — three phasors of equal magnitude, in phase with one another (no mutual shift).
Any real, potentially strongly asymmetric voltage or current condition during a fault can be written exactly as the sum of these three components. The network is then modelled as three separate networks, each symmetrical in itself — and therefore each solvable with a single-phase equivalent circuit — each with its own impedance Z1, Z2 and Z0.
Why three networks instead of one
- Positive-sequence network (Z1): this is the same network that applies under normal, symmetrical operation — the same impedances as in the ordinary short-circuit current calculation of IEC 60909-0.
- Negative-sequence network (Z2): for static equipment (cables, lines, transformers), Z2 is virtually equal to Z1. For rotating machines (generators, large motors), Z2 differs noticeably from Z1, because the rotating field of the negative-sequence current turns in the opposite direction relative to the rotor — see also the guide on negative-sequence protection (46), which is based on this same phenomenon.
- Zero-sequence network (Z0): this network deviates the most, and only exists once an actual return path for the (in-phase) zero-sequence current is present. A delta-connected winding blocks the zero-sequence path to the outside world entirely (the zero-sequence current circulates internally within the delta); an ungrounded star point likewise offers no external zero-sequence path. Only with a grounded star point — directly or via an impedance, see the guide on NGR resistance earthing and the guide on the zigzag earthing transformer, which exists specifically to create a zero-sequence path where none naturally exists — does a path for Z0 exist.
The four fault cases
Each fault type corresponds to a specific way in which the three networks are interconnected:
- Symmetrical three-phase fault (3φ): only the positive-sequence network is involved: Ia1 = Ea / (Z1 + Zf), Ia2 = Ia0 = 0. This is exactly the case that the equivalent-voltage-source method of IEC 60909-0 calculates in its basic form.
- Single line-to-ground fault (1φ-earth, SLG): the three networks are connected in series: Ia1 = Ia2 = Ia0 = Ea / (Z1 + Z2 + Z0 + 3·Zf). The total fault current to earth is then 3×Ia0.
- Phase-to-phase fault (2φ, LL): the positive- and negative-sequence networks are connected in parallel, in opposition, with the zero-sequence network not involved: Ia1 = −Ia2 = Ea / (Z1 + Z2 + Zf).
- Phase-to-phase-to-ground fault (2φ-earth, LLG): all three networks are interconnected in parallel — the most complex combination, with an outcome that, depending on the situation, can come out higher or lower than for the other fault types.
A counter-intuitive consequence: the ground fault can give the highest current
Note: in a solidly or low-resistance grounded network, it is not a given that the symmetrical three-phase fault always produces the highest short-circuit current. When the zero-sequence impedance Z0 is smaller than the positive-sequence impedance Z1 — which can occur close to a solidly grounded star-delta transformer with a relatively low zero-sequence reactance — the calculated current of a single line-to-ground fault can actually exceed that of the symmetrical three-phase fault. Whether this applies to a specific installation depends entirely on the actual Z0/Z1 ratio of that network and that transformer, and must be calculated case by case — this is not a universal rule.
Practical relevance
Symmetrical components are not just a calculation method, but also the basis for several practical protection functions already covered elsewhere on this site: negative-sequence protection (46) detects I2, zero-sequence voltage protection (59N) detects V0, and earth-fault overcurrent protection (50N/51N) detects I0. Understanding where these quantities come from — namely as one of the three components of Fortescue's decomposition — also clarifies why each of these protections is specifically sensitive to the fault type it was designed for, and why, for instance, 50N/51N does not operate on a phase-to-phase fault without earth involvement (where I0 remains zero).
Common mistakes
- Assuming the three-phase fault is always the governing (highest) fault when rating switchgear — at a low Z0/Z1 ratio, a single line-to-ground fault can give the highest current.
- Setting Z2 equal to Z1 for rotating machines — for generators and large motors this is a noticeable simplification that can lead to an incorrect fault current calculation.
- Assuming a zero-sequence path exists where it does not — for example with a delta-connected winding or an ungrounded star point, where Z0 is, in practice, infinite (no path).
- Mixing up the three asymmetric fault types (SLG, LL, LLG) by applying the same network coupling — each fault type has its own specific combination of series/parallel connection of the three networks.
Related
Further reading
- §722Electric Vehicle (EV) Charging Points
- NEN-EN-IEC 62305Lightning protection for greenhouse complexes — risk
- IEC 62305-2Lightning protection — risk assessment and LPL class under IEC 62305-2
- IEC 60364-5-56 / EN 81-72Fire-fighting lifts and safety services — electrical supply per IEC 60364-5-56 and NEN-EN 81-72
- §526 (IEC 60364-5-52)§526 — Electrical connections: why a loose terminal is the most common cause of electrical fire
- §705Livestock buildings and agricultural premises (§705) — earth potential in livestock-accessible zones