Electric Vehicle (EV) Charging Points
§722 — Charging points for electric vehicles (EV)
Section 722 of NEN 1010 (NEN-EN-IEC 60364-7-722) describes the additional requirements for fixed charging points for electric vehicles — wallboxes, public charging stations, and mobile chargers with a fixed connection. The general chapters of NEN 1010 remain applicable; §722 adds conditions specific to charging an EV from the domestic installation.
Scope
§722 applies to:
- Mode 2 — charging via a household socket with an in-cable control box (ICCB).
- Mode 3 — charging via a fixed charging point (wallbox or charging station) with a Type 2 connector.
- Mode 4 — DC fast charging (>22 kW); additional requirements in §722.4.
Not applicable to wireless charging, rolling stock (NEN-EN 50122), and vehicles in motion at charging facilities.
Dedicated circuit (§722.531.2.101)
A separate final circuit is required for each charging point.
Charging an EV draws 16 A – 32 A continuously (over hours). A shared circuit with household loads quickly exceeds the Iz of the cable and triggers thermal tripping of an MCB at the limit of its characteristic. Since NEN 1010:2020, a separate circuit is no longer just a recommendation but a requirement.
Residual-current device protection (§722.531.2.101)
For each EV charging point, the following must be provided:
- Type B RCD or Type A RCD + 6 mA DC detection in the charging point.
Type A alone is not permitted — a leakage current with a DC component (such as may occur in an EV charger during an insulation fault in the battery) "saturates" the toroidal core of a Type A device, deactivating the residual-current function without a tripping signal being issued. Type F is also insufficient; only Type B detects both AC, pulsating DC, and pure DC leakage currents.
The modern practice: wallbox with integrated DC detection + external Type-A 30 mA RCD. Cheaper than a Type-B RCD (€200–€400 versus €30) and functionally equivalent once the wallbox proves compliance with IEC 62752/62955.
Type connector (§722.55)
| Mode | Connector | Power |
|---|---|---|
| 2 | Schuko (type-F) or CEE-blue 16 A | 2.3 kW – 3.7 kW |
| 3 | Type 2 (Mennekes) — fixed on the wallbox | 3.7 kW – 22 kW |
| 4 | CCS Combo 2, CHAdeMO | 50 kW – 350 kW DC |
For Mode 3, type-2 is mandatory in the Netherlands; type-1 (Yazaki) is found only on older Asian vehicles and requires an adapter cable in that case — not fixed on the wallbox.
Load calculation — Pmax × diversity
NEN 1010 §722.311 acknowledges that a wallbox is intended to draw continuous current. For cable and MCB selection:
- Diversity factor 1.0 for a single charging point (no summation with discount for other loads).
- For multiple charging points on a single supply (parking garages, apartments), a load management system (LMS) may be used so that the main supply does not trip. The LMS must comply with IEC 61851-1 §A.4 and have a switching time ≤ 5 s.
Calculation example — 11 kW wallbox
- I = P / (√3 × U × cosφ) = 11 000 / (1,732 × 400 × 1,0) ≈ 16 A per phase.
- Continuous load → use cable Iz table 2-core in conduit (NEN 1010 Table B.52.5), select XMvK 5×2.5 mm² (Iz ≈ 22 A) or YMvK 5×4 mm² (Iz ≈ 31 A) for long distances.
- MCB B16 or C16 — C-characteristic is practical because the wallbox has an input filter with inrush current.
- Type-2 RCD 30 mA or type-A 30 mA + DC-6 mA in the box.
- PE bonding to main earth — required if the wallbox has PME detection (see next paragraph).
PEN-fault detection (§722.411.4.1)
The greatest practical pitfall. In a TN-C-S installation (which accounts for 99% in the Netherlands), the charging point shares the PEN conductor with the grid. When the PEN breaks between the meter and the supply point, the PE of the wallbox — and thus the entire car body — can float to L-potential. In rain or upon contact, this results in a lethal touch voltage.
Therefore, §722.411.4.1 requires:
When using a PME (Protective Multiple Earth / TN-C-S) network, either an own earth electrode must be installed, or PEN-fault detection must be present in the wallbox, which disconnects within 5 s upon interruption of the N/PE.
Practical: all commercial wallboxes (Alfen, Eve, Wallbox, Easee) have PEN detection as standard. Still check the specification — IEC 61851-1 clause 6.3.1.103 is the relevant reference. No PEN detection? Mandatory own earth electrode (Ra such that IΔn × Ra ≤ UL = 50 V → for 30 mA: Ra ≤ 1666 Ω; for 100 mA: Ra ≤ 500 Ω).
SPD (surge protection)
§722.443 refers to the general §443. For charging points located outside (>10 m of cable), a type-2 SPD (8/20 µs, 5–20 kA) on the final circuit is recommended. The wallbox electronics are sensitive to lightning induction, and replacement costs are high (€600–€1500 for a controller board).
Inspection and commissioning
For commissioning, at a minimum:
- Visual inspection — cable routing, mounting height (handle type 2 between 0.5–1.5 m), IP rating for outdoor installation (≥ IP54 for plug, ≥ IP44 for body).
- PE continuity (R ≤ 0.3 Ω at the charging point PE).
- Insulation resistance test L–PE and N–PE at 500 V DC (≥ 1 MΩ).
- Loop impedance Zs from the charging point — Zs × Ia ≤ U0; for B16 in TN ≤ 2.87 Ω, for C16 ≤ 1.44 Ω.
- RCD test — tripping time ≤ 40 ms at 5 × IΔn, ≤ 300 ms at IΔn.
- DC leakage current test — for wallboxes with integrated 6 mA detection: simulate with test source or via diagnostic readout.
- PEN-fault test — break N during charging; wallbox must trip within 5 s.
Include in the inspection report (NEN 1010 §6); sticker with next inspection date ⩽ 1 year (recommendation, no statutory period for domestic use). For commercial charging points, periodic inspection falls under NEN 3140.
Common mistakes
- Wallbox on an existing cooking circuit "because it has 16 A anyway" — no separate final circuit, not compliant with §722.531.2.101.
- Schuko socket as a charging solution — Mode 2 with ICCB is allowed, but ≤ 8 A and the final circuit must be dedicated; drawing 16 A continuously on a Schuko socket melts the contact block.
- Type-AC RCD before the wallbox — no DC detection; an insulation fault in the battery results in undetected leakage current.
- No PEN detection and no earth electrode — the most deadly mistake; often only discovered during a first fault with fatal consequences.
- Reusing the connection cable from the boiler circuit — Iz insufficient for continuous load; thermal degradation of the insulation.
Relationship to other standards
- NEN 3140 — working on an active charging point requires VP/WV status and voltage-free procedure (5 steps).
- IEC 61851 — product standard for wallboxes.
- IEC 62196 — connectors type 1, 2, CCS.
- NEN-EN 50550 — POP (overvoltage protection) — related to §443.
Further reading
- NEN-EN-IEC 60364-7-722 (2018 + A11:2021)
- NEN 1010 Practical Book §722 (Kluwer)
- Netbeheer Nederland — Connection Conditions for Charging Points (capacity tariff)