§531 — Residual Current Devices (RCDs)

Types

TypeDetectsApplication
ACAlternating current (sinusoidal)Obsolete, no longer permitted for new installations
AAlternating current + pulsating DCStandard for residential buildings
FA + high-frequency componentsFrequency inverters (single-phase)
BA + pure DCCharging stations, frequency inverters (three-phase)

Threshold values

  • 30 mA — personal protection in dwellings, bathrooms, outdoors (§411.3.3, §701, §708).
  • 100 / 300 mA — fire protection in agriculture (§705), industry.
  • 500 mA — distribution only, no personal protection.

NEN 1010 explicitly states: every socket outlet up to and including 32 A for general use must be protected by additional protection of maximum 30 mA — this therefore applies not only in dwellings, but to all circuits with this type of connection point, regardless of the room.

ALS or ALA — recognizing the schematic symbol

On a diagram or in a distribution board, an RCD (ALS, residual-current protection only) and an RCBO (ALA, combined residual-current + overcurrent protection in one device) can be distinguished without opening the device itself:

  • RCD (ALS) — the symbol shows only the differential-current bar, without the curved S-shape/rectangle of a circuit breaker and without a B/C/D letter. The stated amp value is the rated residual current / let-through current (the maximum current the device may pass), not a thermal protection value.
  • RCBO (ALA) — combines the circuit-breaker symbol (with a B/C/D letter) with the residual-current symbol in one block. Here, the amp value is indeed the rated current In of the integrated circuit breaker.

Do not confuse the two when reading a diagram: an RCD does not protect a cable against overload, an RCBO does.

Testing with the installation tester

An RCD is checked with an installation tester at three points, not just one:

  • At I∆n (the rated tripping current) the RCD must trip within ≤ 300 ms.
  • At 5 × I∆n the RCD must trip faster: ≤ 40 ms.
  • At ½ × I∆n the RCD must not trip — an RCD that already trips here is set too sensitively or is defective, causing nuisance tripping.
  • A selective type S RCD trips with a delay, between 130–500 ms, so that a downstream fast RCD gets the first chance to trip.

Besides this measurement with the installation tester, the manual test button (T-button) on the device itself remains a separate, simpler check — an operation that even a layperson may carry out, at least once every six months.

Practical installation

  1. RCD before the final circuits, after the main fuse.
  2. Test button at least once every six months (recommendation: quarterly).
  3. No shared neutral conductors between different RCD groups.
  4. Cumulative leakage currents must remain < 30% of I∆n; otherwise, use type B or multiple RCDs.