Flame-Retardant vs. Fire-Resistant (Cable)
Two distinct, non-interchangeable cable properties that are often confused: a flame-retardant cable (tested to NEN-EN 60332-1) prevents flame propagation along the cable once the ignition source is removed, but gives no guarantee that the cable keeps functioning during a fire. A fire-resistant cable (functional integrity cable, tested to NEN-EN 50200 with a PH classification) continues to operate electrically for a specified time (e.g. PH30, PH60, PH90) during a fire, even while the cable itself is burning. Every fire-resistant cable is by definition also flame-retardant, but the reverse is not true: an ordinary flame-retardant installation cable is not suitable for circuits that must keep functioning during a fire, such as fire alarm systems, sprinkler pumps and smoke extraction.
Bij de aansluiting van een sprinklerpomp schrijft de brandveiligheidsadviseur een FE180/PH90-kabel voor in plaats van een gewone halogeenvrije installatiekabel, omdat de voeding tijdens een brand van 90 minuten operationeel moet blijven.
Een halogeenvrije, vlamvertragende kabel (bijvoorbeeld NHXH zonder PH-classificatie) toepassen voor een brandmeldcentrale-voeding in de veronderstelling dat 'halogeenvrij' hetzelfde is als 'brandwerend' — zonder PH-classificatie en functiebehoudstest is functiebehoud tijdens brand niet aangetoond.
See also
- → NEN-EN 1366-3 Fire-resistant cable penetrations — NEN-EN 1366-3
- → EN 13501-2 Fire-protective coating on cable trays and ladders — intumescent cable protection systems
- → IEC 60364-5-52 Bijlage B (Cg) Grouping factor Cg — why bundled cables may carry less than separated cables
- → NEN-EN 50575 / NEN 8012 Fire classification of cables — CPR (NEN-EN 50575) and NEN 8012
- → IEC 61914 (cable cleats) Cable cleats — short-circuit withstand per IEC 61914
- → IEC 61442 Cable joints — underground cable connections and repairs (IEC 61442)