Step Voltage (Earth Potential Gradient)
The voltage difference that arises between two points on the ground separated by roughly one human stride (typically taken as 1 m), caused by the potential gradient around an earth electrode when a fault current flows through it. Unlike touch voltage (between a conductive part and the ground), step voltage arises solely through the ground itself, between the feet of a person standing in or near the potential gradient, and can rise dangerously high with high fault currents and a poorly distributed earth electrode (such as a single rod electrode instead of a ring earth electrode), particularly close to the current injection point. A well-designed earthing system — for example a flat ring earth electrode or meshed earth grid instead of a point electrode — flattens the potential gradient and thereby limits step voltage.
Bij het ontwerp van de aarding voor een middenspanningsstation in een weiland kiest de ontwerper voor een vermaasd aardnet in plaats van een enkele staafelektrode, specifiek om de stapspanning voor omstanders en vee bij een aardfout te beperken.
Alleen de aanrakingsspanning bij een verdeelkast beoordelen en de stapspanning rond een buiten gelegen aardelektrode (bijvoorbeeld bij een transformatorstation) over het hoofd zien — juist in de directe omgeving van de elektrode kan de stapspanning het kritische risico zijn, niet de aanrakingsspanning.
See also
- → §411 Protective earthing (PE)
- → §705 Livestock buildings and agricultural premises (§705) — earth potential in livestock-accessible zones
- → §715 / IEC 60364-7-715 §715 — Extra-low-voltage lighting installations
- → §443 Surge Protection (SPD)
- → §411 Automatic Power Off (AUV)
- → §413.3 Electrical separation (§413.3) — an isolating transformer as a protective measure without earthing