Cable Fire Propagation — Single Cable vs. Bunched Test
The distinction between two cable fire-testing methods that are often confused: IEC 60332-1 tests whether a single, vertically suspended cable self-extinguishes after exposure to a gas flame for a set time (the flame must not propagate beyond a specified distance along the cable), whereas IEC 60332-3 simulates a more realistic scenario in which multiple cables are bundled — as in a cable tray or on a cable ladder in practice — suspended vertically and exposed to a flame. A cable that successfully passes the IEC 60332-1 test often still fails the IEC 60332-3 bunched test, because the stacking of combustible cable sheath materials in a bundle causes a much greater thermal load and an increased risk of flame propagation via neighbouring cables than is the case with an isolated cable. For applications where multiple cables are laid close together in cable trays or ladders, NEN 1010 and building regulations therefore prescribe bunch-tested cables (or an equivalent fire-resistant measure), even if the individual cable already passes the simpler single-cable test.
Bij het ontwerp van een hoofdverdeelinrichting met tientallen parallelle voedingskabels in een gemeenschappelijke kabelgoot eist de brandveiligheidsadviseur kabels met een geldig IEC 60332-3-certificaat, omdat een enkelvoudig IEC 60332-1-certificaat onvoldoende zekerheid geeft over het gedrag bij brand in die specifieke, dicht bepakte configuratie.
Aannemen dat een kabel die 'zelfdovend' is getest (IEC 60332-1) automatisch ook geschikt is voor toepassing in een dicht bepakte kabelgoot met tientallen andere kabels — de bundelbeproeving IEC 60332-3 test een fundamenteel ander, realistischer brandscenario.
See also
- → NEN-EN 1366-3 Fire-resistant cable penetrations — NEN-EN 1366-3
- → IEC 60364-5-52 Bijlage B (Cg) Grouping factor Cg — why bundled cables may carry less than separated cables
- → EN 13501-2 Fire-protective coating on cable trays and ladders — intumescent cable protection systems
- → IEC 60445 / NEN 1010 §514 Cable identification & marking — ferrules, nameplates and cable numbering
- → IEC 62444 / EMC Choosing a cable gland — IP rating, strain relief, and EMC shielding
- → Bijlage G / IEC 60364-5-52 Cable resistance (R) and reactance (X) in voltage-drop calculations — when X may and may not be neglected