NEN 1010 §521.9
Fire-resistant cable (NHXH / FE180)
Brandveilige kabel (NHXH / FE180 E30)
Also known as: nhxh, fe180, brandveilige-kabel, fire-resistant-cable, halogeenvrije-kabel, halogen-free-cable, noodverlichting-kabel
Halogen-free, flame-retardant cable (NHXH / FE180) maintaining functionality for 30–90 minutes during fire (FE30/FE60/FE90). Mandatory for safety installations like emergency lighting, fire alarm panels, sprinkler pumps, and smoke extraction. No chlorine or bromine sheath — no hydrochloric acid fumes when burning.
Practical example
Fire-safe cable (NHXH / FE180 E30). The emergency lighting and smoke extraction wiring in an office building is installed in NHXH FE90, ensuring 90 minutes of operation during fire.
Common mistake
Fire-safe cable (NHXH / FE180 E30). Common mistake: Using standard YMvK for emergency lighting — in a fire, the sheath melts, causing the safety system to fail exactly when needed.
See also
Related terms
In-depth guides
- → §423 (IEC 60364-4-42) §423 — Protection against burns: maximum accessible surface temperatures (Table 42.1)
- → §433 Overload protection (§433) — the coordination rule Ib ≤ In ≤ Iz and I₂ ≤ 1.45 Iz
- → §559 Assimilation lighting — groups, RCD type and protection
- → IEC 62619 / IEC 62477-1 BESS — DC side: overcurrent protection and cable sizing for battery energy storage systems
- → NEN-EN-IEC 62305 Lightning protection for greenhouse complexes — risk
- → §422 (IEC 60364-4-42) Fire-risk premises (§422, BE2) — the 300mA RCD requirement and non-flame-propagating cabling