NEN-Hub
🔍
IEC 60364-5-54 §543.7

High Protective-Conductor-Current Equipment — Fixed Connection Required

Apparatuur met hoge aanraakstroom — vaste aansluiting vereist

Electrical equipment (such as large variable frequency drives, IT server racks with many switch-mode power supplies, or medical imaging equipment) whose normal, operational protective-conductor current (leakage current to earth via the PE conductor) exceeds 10 mA per IEC 60364-5-54 §543.7. Such equipment is subject to additional requirements: either a PE conductor with a minimum cross-section of 10 mm² copper (or an equivalent duplicated PE conductor, each with the normal minimum cross-section and its own independent terminal), or automatic disconnection upon interruption of the PE conductor, or a fixed connection (no plug-and-socket connection) so that the continuity of the earth connection does not depend on an easily disconnectable connector. The purpose is to prevent someone touching the metal enclosure during operation from experiencing a touch current that, although below the hazard threshold, would be perceived as unpleasant or alarming if the PE were accidentally interrupted.

Practical example

Een serverkast met 40 schakelende voedingen heeft een cumulatieve aanraakstroom van 35 mA gemeten; de installateur kiest voor een vaste aansluiting met een 10 mm² PE-geleider in plaats van een stekker-wandcontactdoosverbinding.

Common mistake

Grote IT-installaties met veel schakelende voedingen op een gewone 2,5 mm² groep met stekker aansluiten zonder de cumulatieve aanraakstroom te berekenen — bij meer dan 10 mA gelden de aanvullende eisen van §543.7, ongeacht of de individuele apparaten op zich probleemloos lijken.

See also

Beschikbaar in: English, Nederlands, Polski, Русский, Українська
High Protective-Conductor-Current Equipment — Fixed Connection Required — dictionary · NEN-Hub