NEN 1010-5-52 / IEC 60364-5-52 bijlage E

Third-harmonic (triplen) neutral conductor loading

Derde-harmonische belasting van de nulgeleider

A phenomenon where, with non-linear single-phase loads (LED drivers, computers, variable-frequency drives), the third harmonic and its multiples (triplens) in the three phases are in phase with each other rather than cancelling out, so they add up in the neutral conductor instead of disappearing. This can make the current in the N conductor higher than in any individual phase conductor, even though the neutral traditionally has the same (or a smaller) cross-section. NEN 1010-5-52 therefore requires an oversized or duplicated neutral conductor, or a derating factor on cable current-carrying capacity, where significant third-harmonic loading is present.

Practical example

Bij een kantoorverdieping vol led-verlichting en pc's meet de installateur met een stroomtang een N-stroom die 40% hoger is dan de gemiddelde fasestroom, en past daarom een verzwaarde nulgeleider toe.

Common mistake

Aannemen dat de nulgeleider bij een gebalanceerde driefasenbelasting altijd stroomloos of laagbelast is — bij veel niet-lineaire eenfasige apparatuur geldt dit juist niet.