Vector shift protection (ANSI 78) — an alternative islanding-detection method alongside ROCOF
Vector shift protection (ANSI 78) — an alternative islanding-detection method alongside ROCOF
The guide on frequency protection and ROCOF (81O/81U/81R) briefly mentions a phase shift (vector shift) as an alternative, passive method for islanding detection in distributed generation, alongside ROCOF. This article looks at that method in more depth: vector shift protection, ANSI 78.
The principle: monitoring the phase angle, not the frequency
Ordinary frequency protection (81O/81U) and ROCOF (81R) both monitor the frequency of the voltage — its absolute level and its rate of change, respectively. A vector shift relay instead monitors the phase angle of the voltage waveform relative to an internal reference derived from the preceding cycle(s). As long as a generator runs synchronously with the grid, this phase angle barely changes from cycle to cycle. If the grid disconnects while the generator keeps running, the load impedance "seen" by the generator changes abruptly, and the generator rotor — which, due to its own inertia, cannot instantly follow — responds with a sudden, measurable jump in the phase angle of the generated voltage relative to the expected trajectory. If this jump exceeds a set threshold (typically a few degrees), the relay operates.
Why vector shift can respond faster than ROCOF under a light imbalance
ROCOF protection needs a detectable signal arising from a real power imbalance between generation and load within the newly formed island: the smaller that imbalance at the moment of islanding, the smaller and slower the resulting frequency change, and the harder it is for ROCOF to recognize the island in time. A vector shift, by contrast, can occur at the very moment of disconnection itself, even when the generator happened to be supplying almost exactly its own island load just before disconnection — the abrupt impedance jump felt by the rotor is largely independent of how small the resulting power imbalance turns out to be. This makes vector shift protection, in practice, attractive as a supplementary, not a replacement, detection method alongside ROCOF and ordinary voltage/frequency limits.
The same vulnerability as ROCOF: nuisance tripping
Like ROCOF, a vector shift relay is sensitive to events that have nothing to do with islanding but do cause a sudden phase-angle change:
- A severe fault elsewhere in the network (for example a short circuit on a neighbouring feeder) can cause a temporary phase jump during the fault interval that recovers once the fault is cleared — in that case the generator remains connected and should not disconnect.
- Starting a large motor elsewhere in the same network can cause a similar, momentary phase-angle disturbance.
To limit nuisance tripping from such events, a vector shift relay is typically combined with a short blocking time after detecting a phase jump that is not followed by a sustained deviation, and with the same voltage supervision used with ROCOF and ordinary frequency protection to prevent operation in a network that is already nearly de-energized.
Practical relevance
When assessing the anti-islanding settings of an inverter or a synchronous generator connected to the public grid under NEN-EN 50549-1, it must be established which combination of detection methods is actually active: ROCOF only, vector shift only, or both combined with voltage/frequency limits. An inverter relying on vector shift alone may respond more slowly than expected in a network with a coincidentally very small power imbalance at the moment of islanding, if the phase jump happens to be small in that specific case; conversely, a generator relying on ROCOF alone may miss a vector-shift-sensitive situation where the imbalance happens to be very small but the impedance jump is still clearly present.
Common mistakes
- Confusing vector shift protection (78) with ROCOF (81R) — both are passive islanding-detection methods, but they measure a fundamentally different signal (phase-angle jump versus rate of frequency change).
- Assuming vector shift is inherently faster than ROCOF — this depends on the specific situation; with a large power imbalance at islanding, ROCOF may in fact operate faster.
- Not accounting for nuisance tripping from severe network faults or motor starts elsewhere in the network, which can cause unwarranted disconnection of distributed generation without an island actually having formed.
- Applying only one of the two detection methods where the standard or the grid operator requires a combination, increasing the risk of missed island detection in the specific case where that one method performs poorly.
Related
Further reading
- Praktijk (ANSI 81, ROCOF)Frequency protection (ANSI 81) and ROCOF — how a relay recognises loss of grid by the speed of frequency change
- Praktijk (ANSI 46)Negative-sequence protection (ANSI 46) — why phase unbalance heats a motor faster than the current alone suggests
- Praktijk (ANSI 27/59)Undervoltage and overvoltage protection (ANSI 27/59) — why a generator or motor also needs protection against its own terminal voltage
- ANSI 78 (poolslip/out-of-step)Pole-slip / out-of-step protection (ANSI 78) — asynchronous operation of a generator
- ANSI 50/51 (IDMT-curven)Overcurrent protection (ANSI 50/51) — IDMT time-current characteristics
- ANSI 85 (teleprotectie)Teleprotection schemes (ANSI 85) — permissive and blocking with distance protection