Swimming pool/pond zone classification
Classification of the area around a swimming pool, pond or similar body of water into zones 0, 1 and 2 under NEN 1010 §702, each with its own requirements for voltage, IP protection and permitted equipment. Zone 0 is the water itself (SELV/PELV only, max. 12 V AC or 30 V DC, IPX8); zone 1 extends 2 m horizontally and 2.5 m vertically from the edge (no socket-outlets, lighting only SELV/PELV or double-insulated); zone 2 extends a further 1.5 m (socket-outlets only behind a 30 mA RCD and minimum IPX4). Differs from the bathroom zone classification (§701) in its larger distances and the additional requirement for supplementary equipotential bonding of all conductive parts in and around the basin.
Bij de aanleg van een buitenzwembad wordt de onderwaterverlichting uitgevoerd als SELV 12 V (zone 0), terwijl de circulatiepomp met vaste bedrading buiten zone 1 wordt geplaatst en alle metalen delen (leuning, pomphuis, wapening van het bassin) worden opgenomen in de aanvullende equipotentiaalverbinding.
Een gewone spatwaterdichte buitencontactdoos in zone 1 plaatsen 'omdat hij toch IP44 is' — in zone 1 zijn wandcontactdozen sowieso verboden, ongeacht de IP-classificatie; ze mogen pas vanaf zone 2 met de juiste aardlekbeveiliging.
See also
- → §702 Swimming pools and fountains (§702) — zones, SELV and supplementary bonding
- → §411 Protective earthing (PE)
- → §411 Automatic Power Off (AUV)
- → §413.3 Electrical separation (§413.3) — an isolating transformer as a protective measure without earthing