IEC 60156

Transformer Oil Breakdown Voltage Test (BDV Test)

Doorslagspanningstest transformatorolie (BDV-test)

A laboratory or field test per IEC 60156 in which a sample of transformer oil between two sphere electrodes at a defined gap (typically 2.5 mm) is subjected to a steadily rising AC voltage until a spark-over (breakdown) occurs; the average of several measurements yields the Breakdown Voltage (BDV), expressed in kV. A low BDV indicates contamination of the oil with moisture, particles or conductive pollution and points to reduced dielectric strength and hence an increased risk of internal breakdown in the transformer. The BDV test is a quick, relatively inexpensive routine test often performed alongside moisture content and dissipation factor measurements, but — unlike gas-in-oil analysis (DGA) — it gives no information about faults that have already occurred internally.

Practical example

Tijdens het periodiek onderhoud van een vermogenstransformator laat de inspecteur een oliemonster nemen voor een BDV-test volgens IEC 60156; een uitkomst onder de norm geeft aanleiding tot filtratie of vervanging van de olie.

Common mistake

Een lage BDV-uitkomst uitsluitend toeschrijven aan de olie zelf, terwijl vochtige of vervuilde monsterflessen en onzorgvuldige monstername een even grote oorzaak van een lage meetwaarde kunnen zijn.