Relative Humidity and Condensation in Switchgear Cabinets
The monitoring of relative humidity inside a switchgear or distribution cabinet, where an excessively high value — often caused by day/night temperature fluctuations, insufficient ventilation or a poorly sealed cabinet entry — can lead to condensation on cold metal parts once the temperature drops below the dew point. Condensation moisture on busbars, terminals and circuit boards increases the risk of tracking currents, corrosion and eventually short circuits, and is a known, often underestimated cause of failures in outdoor or unheated cabinets, such as at wind turbines, transmission masts or underground installations. NEN-EN 61439 requires a suitable environmental classification for switchgear and controlgear assemblies, and control measures such as cabinet heating, thermostatically controlled ventilation or the use of moisture-absorbing agents are applied to structurally keep relative humidity below the level at which condensation can occur.
Bij een buiten opgestelde verdeelkast bij een windturbine plaatst de installateur een vochtsensor met datalogging, zodat bij een structureel te hoge relatieve luchtvochtigheid tijdig actie kan worden ondernomen voordat condensatie tot corrosie of kortsluiting leidt.
Kastverwarming of ventilatie alleen op basis van de omgevingstemperatuur regelen, terwijl juist het temperatuurverschil tussen dag en nacht — en dus het bereiken van het dauwpunt — de werkelijke oorzaak van condensatie is.
See also
- Dynamic Resistance Measurement (DRM) — Circuit Breaker Contacts During Switching
- Verifying absence of voltage
- Sound Emission Measurement (Transformer, Switchgear, dB(A))
- No-Trip Loop Impedance Test Method
- Voltage Transformer (VT) — Accuracy Class and Burden
- Earth Resistance — Seasonal Variation (Frost/Drought)