NEN 1010 §411.4

PEN Conductor Break (Elevated Potential, TN-C-S)

PEN-geleiderbreuk (verhoogd potentiaal, TN-C-S)

A fault condition in the TN-C section of a TN-C-S network (for example an underground or overhead distribution cable using a combined neutral-earth conductor) in which the PEN conductor is interrupted between the transformer and the point where it splits into the installation, for example due to corrosion, excavation damage or a poor connection. Because both PE and N are derived from the PEN conductor after the split point, a PEN break not only causes the neutral conductor to lose its earth reference, but also raises all earthed metal parts (enclosures, conduit, PE cores) of the connected installations to a potential equal to the load imbalance in the network — in severe cases nearly the full phase voltage, with direct electrocution risk on touching normally earthed parts. This risk is a key reason why, in the Netherlands, new installations preferably use TN-S from the connection point onward, and why PEN conductors in distribution networks must be more heavily dimensioned and better monitored than an ordinary N conductor.

Practical example

Na meldingen van tintelingen bij het aanraken van een tuinhek en een wasmachinebehuizing in dezelfde straat onderzoekt de netbeheerder de PEN-geleider van de betreffende laagspanningskabel en vindt een corrosiegerelateerde onderbreking als oorzaak van de verhoogde potentialen op de aangesloten installaties.

Common mistake

Bij het onderzoeken van een klacht over 'tintelend water' of een schokkend gevoel bij een metalen kraan alleen de eigen installatie van de klant controleren, terwijl de oorzaak — een PEN-breuk verderop in het openbare net — buiten de installatiegrens ligt en alleen door de netbeheerder kan worden verholpen.

See also

Beschikbaar in: English, Nederlands, Polski, Русский, Українська