IDMT Relay Characteristic (Inverse Definite Minimum Time)
A protection characteristic of an overcurrent relay in which the tripping time is inversely proportional to the magnitude of the fault current: the higher the current above the setting, the faster the relay trips, down to a minimum floor at very high currents. IEC 60255-151 defines standardised curves such as Standard Inverse (SI), Very Inverse (VI) and Extremely Inverse (EI), each with its own mathematical formula relating tripping time to the multiple of the set current. This characteristic enables time-current graded discrimination between successive protection relays in a network: relays closer to the source are given a longer characteristic time than relays closer to the fault, so that on a fault only the nearest relay trips.
Bij de instelling van de beveiligingsrelais in een industrieel middenspanningsnet kiest de beveiligingsingenieur een Very Inverse-karakteristiek voor het relais aan de voedingszijde, zodat dit relais bij een fout verderop in het net voldoende tijd laat aan de onderliggende relais om eerst uit te schakelen.
Voor alle relais in een net dezelfde IDMT-curve en tijdmultiplier instellen zonder een selectiviteitsstudie uit te voeren — hierdoor kunnen bij een fout meerdere relais tegelijk of in de verkeerde volgorde uitschakelen, wat een groter deel van de installatie onnodig spanningsloos maakt dan nodig.