NEN-Hub
🔍
NEN-EN 60228 / IEC 60502-1

Insulation Temperature Class (PVC/XLPE)

Isolatie-temperatuurklasse (PVC/XLPE)

The maximum permitted operating temperature of the conductor insulation, which determines a cable's current-carrying capacity: PVC-insulated cables (e.g. YMvK, VOB) are rated for a maximum continuous operating temperature of 70°C, while XLPE-insulated cables (cross-linked polyethylene, used in many modern installation and underground cables) can withstand up to 90°C. This 20°C temperature difference gives XLPE cables a considerably higher current-carrying capacity than PVC at the same cross-section, which is why XLPE is often preferred for heavier loads; the short-circuit temperature (for brief periods) is even higher for both types (160°C for PVC, 250°C for XLPE).

Practical example

Bij het herberekenen van de belastbaarheid van een bestaande YMvK-kabel (PVC, 70°C) die wordt vervangen door een XLPE-kabel van dezelfde doorsnede, kan de installateur een hogere stroombelastbaarheid aanhouden volgens de belastbaarheidstabellen van NEN 1010.

Common mistake

Bij het combineren van een nieuwe XLPE-kabel met oude PVC-eindafwerkingen of -moffen de belastbaarheid van de XLPE-kabel (90°C) aanhouden, terwijl de zwakste schakel — vaak de oudere PVC-component — de daadwerkelijke maximale bedrijfstemperatuur van het geheel bepaalt.

See also

Beschikbaar in: English, Nederlands, Polski, Русский, Українська
Insulation Temperature Class (PVC/XLPE) — dictionary · NEN-Hub