NEN-Hub
🔍
NEN-EN 1838

Anti-Panic Lighting (Open-Area Lighting)

Antipaniekverlichting (open-ruimteverlichting)

A category of emergency lighting under NEN-EN 1838, separate from escape-route lighting, intended to prevent panic in large, open areas (for example a shop floor, foyer or meeting room with a floor area greater than about 60 m²) by providing sufficient horizontal illuminance (at least 0.5 lux on the floor, outside a 0.5 m border along the walls) when normal lighting fails, so that occupants can safely reach an escape route or exit. Unlike escape-route lighting, which illuminates narrow walking routes and pictograms, anti-panic lighting covers the entire open floor area, and unlike high-risk task-area lighting (which requires a much higher level to safely shut down a hazardous process), anti-panic lighting focuses solely on orientation and preventing panic.

Practical example

Bij het ontwerp van de noodverlichting voor een grote supermarkt met een verkoopvloer van 400 m² rekent de installateur naast de vluchtwegverlichting boven de nooduitgangen ook antipaniekarmaturen in het gangenpatroon, zodat het volledige vloeroppervlak bij stroomuitval minimaal 0,5 lux behoudt.

Common mistake

Bij een grote open kantoorruimte alleen vluchtwegverlichting boven de deuren en langs de hoofdroutes plaatsen en de rest van de open vloeroppervlakte donker laten — voor ruimten boven de drempelwaarde van NEN-EN 1838 is aanvullende antipaniekverlichting over de volledige oppervlakte verplicht.

See also

Beschikbaar in: English, Nederlands, Polski, Русский, Українська
Anti-Panic Lighting (Open-Area Lighting) — dictionary · NEN-Hub